Veris Industries Badger 3000 SERIES Install User Manual

Page 4

Advertising
background image

4

Analog Input

As an alternative to the Pulse Inputs the Series 3000

can accept a Analog input. The input is non-isolated, but

can accept 0-1VDC; 0-5VDC; 0-10VDC; 0-20mA; and

4-20mA with both factory defined, and custom units of

measure.

Low impedance 100 Ohm input for current inputs optimiz-

es performance and flexibility or loop power supplies.

Both the Low and High end scaling are independent, and

field configured by the installer.

See Programming Flow Chart for required input con-

figuration

Analog Input Wiring

Solid State Switch and Form “C” Output Wiring

The Badger

®

Data Industrial

®

Series 3000 has one Nor-

mally Open (N.O.) solid state switch, and one Solid State

Form “C” Relay.

Check the specifications page for maximum voltage and

current ratings for each type output.

These outputs are completely independent, electrically

isolated, and can be programmed as either Pulse, or Set-

point outputs.

When the function “Totalizer” is selected the unit of mea-

sure and resolution are independent from the displayed

units, and can be programmed where 1 pulse occurs

once every 0000000.1 to 999999999.of units selected,

with any pulse width from 0001 to 9999mS.

When the “Alarm” is selected as the unit of measure and

the resolution is independent from the displayed units, it

allows the unit to be programmed as either a High or Low

rate Set Point. Since the Set-point, Release Point, and

their associated time delays are fully independent this

output can be either a classical High Rate, or Low Rate

alarm depending on the settings selected. When design-

planning keep in mind that although both of these outputs

can be programmed as alarm points only the Relay pro-

vides both N.O. and N.C. contacts. The switch is a simple

N.O. contact.

Examples:

High Flow Set-Point

The Set-Point

“SETPT” must be a value greater than

the Release Point

“RELP.”

The Relay output will have continuity between its “N.C”.

terminal and “COM” until the flow has exceeded the Set-

Point

“SETPT” for a continuous period of time exceeding

the Set-Point-Delay

“SDLY”, at which time the N.C. con-

nection will open, and the N.O. contact will have continu-

ity to the “COM” terminal. When the flow has dropped

below the Release Point

“RELP” for a continuous period

of time exceeding the

“RDLY” the relay states will return

1 ANALOG IN+

2 ANALOG IN-

3 SHIELD

4 SENSOR IN

5 GND

6 SHIELD

7 SENSOR PWR

Figure 4: Data Industrial Flow Sensor

Wiring Examples

(Two and Three Wire Pulse Types)

1 ANALOG IN+

2 ANALOG IN-

3 SHIELD

4 SENSOR IN

5 GND

6 SHIELD

7 SENSOR PWR

Figure 5: 4-20mA Analog Loop Powered Wiring

Figure 6: Voltage or Current Sourcing Analog Inputs

1 ANALOG IN+

2 ANALOG IN-

3 SHIELD

4 SENSOR IN

5 GND

6 SHIELD

7 SENSOR PWR