Veris Industries H81xx SERIES Datasheet User Manual

Energy meters, H81xx series, Po wer/ener g y monit oring

Advertising
background image

p

o

wer/ener

g

y monit

oring

VERIS INDUSTRIES

800.354.8556

+1 503.598.4564

www.veris.com

Simple System Integration with a

Variety of Protocol Options Available

Energy Meters

FEATURES

Revenue Grade measurements

High resolution backlit LCD display provides clear readings at a distance...

reduces the risk of misinterpretation of the data. Back-lighting can be disabled

if desired

H8163 provides a pulse output from 1/10 to 1 pulse per kWh for easy connection

to existing control or data acquisition systems

Provides a phase-loss alarm...protects equipment (H8163)

With the optional communications board (H81xx-CB), the H81xx can easily be

added to a Modbus, BACnet or N2 control system network to report multiple

variables including kW, kWh, kVAR, PF, Amps and Volts, providing crucial power

information at a reduced installation cost

DESCRIPTION

The H81xx Series Energy Meters are easy to install and provide exceptional system
accuracy, making them ideal for all submetering applications.

Each meter is factory-matched with one to three split-core CTs. The meter/CT pairs
are system-calibrated to provide excellent total system accuracies of 1% from 2%
to 100% of the amperage rating of the CTs (e.g., 2-100 amps with 100 amp CTs).
Matching serial numbers assure that the meter and CT were calibrated together
(matching does not apply if using 100A CTs).

The H81xx is easy to install. The split-core CTs eliminate the need to remove
electrical conductors, reducing installation time. The meter is also capable of
detecting and correcting phase reversal, eliminating the need for concern about
CT load orientation. The convenient color coding of the CTs and voltage leads make
correct connection simple.

APPLICATIONS

Commercial tenant submetering

Performance contracting

Allocating costs

Real-time power monitoring via local display or through control/data

acquisition systems

SPECIFICATIONS

Inputs:

Voltage Input

H8150

90-132VAC line-to-neutral

H8163

90-300VAC line-to-neutral

Accuracy:

System Accuracy

±1% of reading from 2% to 100% of the rated current of the CTs, accomplished by matching the CTs with electronics and calibrating them as a system

Sample Rate

1280 Hz

Outputs:

All Models

LCD Display

1.2” x 3.8” (31 mm x 97 mm) viewing area, 160 segments, backlit with LCD

H8163 Only

Pulse Output

Normally open, Opto-FET, 100mA@24VAC/DC

Pulse Rate

0.10*, 0.25**, 0.50, or 1.00kWh per pulse

Pulse Width

200 msec closed

Phase Loss Alarm

N.O. (opens on alarm), Opto-FET, 100 mA @ 24 VAC/DC; fixed threshold 25% below

Mechanical:

Protection Class

NEMA 1

Environmental:

Operating Temperature Range

0° to 50°C (32° to 122°F)

Storage Temperature Range

-40° to 70°C (-40° to 158°F)

Humidity Range

0-95% noncondensing

Agency Approvals UL61010

Approved for California CSI Solar applications (check the CSI website for model numbers).

*not supported at >1600A

**not supported at >2400A

Note: Meter and CTs serial numbers must match, except for 100A CTs. Neutral voltage connection is required.

H81xx

Year

Warranty

5

H81xx SERIES

HQ0001813.B 01131

Advertising