Veris Industries VH7200 SERIES Install User Manual

Page 11

Advertising
background image

11

Config.

parameters

Significance

Default value

Adjustments

Dhu OALK

Dehumidification outside air

temperature lockout

Default value = -40°F (-

40°C)

Outside air temperature under which the dehumidification sequence is

disabled.

Only valid if an outdoor air sensor is connected at the humidistat or a network

value is transmitted to the humidistat.

From –40°F up to 122°F (-40°C to 50°C)

HL Hyst

High Limit hysterisys

Default value = 5% RH

High Limit control hysterisys.

Used only if sequence uses 2 position humidity controle

2 = 2Pdh and 4 = 2Phu2Pdh

From 2% RH up to 20% RH

cal RH

Humidity sensor calibration

Default value = 0 %RH

Offset that can be added/subtracted to actual displayed humidity by ± 15.0

%RH.

This calibration applies to the internal humidity sensor if no remote humidity

sensor is connected. This calibration applies to the remote humidity sensor

when one is connected.

From –15% RH up to 15% RH

cal OS

Outside air temperature

sensor calibration

Default value = 0.0 °F or °C

Offset that can be added/subtracted to the displayed outside air temperature

± 5.0 °F ( ± 2.5 °C )

RH LT

Reset RH lower outside

temperature setpoint

Default value = -20°F (-

29°C)

Minimum outside air temperature for RH setpoint reset.

Only valid if an outdoor air sensor is connected at the humidistat or a network

value is transmitted to the humidistat. See RH HT & RE Sp.

From –40°F up to 15°F (-40°C to –9.5°C)

RH HT

Reset RH higher outside

humidity setpoint

Default value = 32°F (0°C)

Maximum outdoor air temperature for RH setpoint reset.

Only valid if an outdoor air sensor is connected at the humidistat or a network

value is transmitted to the humidistat. See RH LT & RE Sp

From 20°F up to 55°F (-6.5°C to 12.5°C)

RE Sp

Reset humidity setpoint

Default value = 20% RH

The RH setpoint will be reset from the user setpoint to this value when the RH

LT outside air humidity value is reached.

Only valid if an outdoor air sensor is connected at the humidistat or a network

value is transmitted to the humidistat. See RH LT & RE HT.

From 10% RH up to 90% RH

HL Sp

RH High limit setpoint

Default value = 85% RH

High humidity limit in the supply.

Only valid if a 0-5 Vdc sensor is connected at the humidistat – otherwise this

feature is disabled automatically.

From 50% RH up to 90% RH