CURRENT MONITORING

INSTALLATION GUIDE

Z201983-0K

PAGE 1

©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

03132

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

Split-Core Current Switch,

Fixed Trip Point

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

• Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.

Failure to follow these instructions will result in death or serious injury.

A qualified person is one who has skills and knowledge related to the construction and

operation of this electrical equipment and the installation, and has received safety

training to recognize and avoid the hazards involved.

NEC2009 Article 100

No responsibility is assumed by Veris Industries for any consequences arising out of the

use of this material.

DANGER

WIRING EXAMPLE

TM

600

DIMENSIONS

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.

• The installer is responsible for conformance to all applicable codes.

• Mount this product inside a suitable fire and electrical enclosure.

Motor

Fan

DDC CONTROLLER

DI

CONTACTOR

Insulated Conductor ONLY

2.5" *

(64 mm)

2.1"

(54 mm)

3.5"

(89 mm)

2.9"

(74 mm)

0.4” x 0.2”

(10 mm x 5 mm)

Slot (2x)

1.2"

(31 mm)

Removable Mounting Bracket

0.7"

(18 mm)

0.5"

(13 mm)

2.1"

(54 mm)

1.0" *

(26 mm)

0.6"

(16 mm)

RoHS

Compliant

SPECIFICATIONS

Sensor Power

Induced from monitored conductor

Amperage Range

0.15 to 200A Continuous

Status Output Ratings

N.O. 1.0A@30VAC/DC not polarity sensitive

Insulation Class

600VAC RMS (UL), 300VAC RMS (CE)

Setpoint

Fixed at 0.15 A max. (60 Hz)

Frequency

50/60 Hz

Temperature Range -15° to 40°C (5° to 104°F)

Humidity Range

10-90% RH non-condensing

Off State Resistance

Open switch represents 1+ MΩ

On State Resistance

Closed switch represents <200 mΩ

Terminal Block Wire Size

14 to 24 AWG (2.1 to 0.2 mm

2

)

Terminal Block Torque

3.5 to 4.5 in-lb (0.4 to 0.5 N-m)

Agency Approvals

UL508, CE: EN61010-1

Installation Category

Cat. III, pollution degree 2

For CE compliance, conductor shall be insulated according to IEC 61010‑1.

The product design provides for functional insulation only.

Listed for use with 75°C insulated conductors.

INSTALLATION

Disconnect and lock out power to the enclosure
containing the condustor to be monitored.

1. Locate a mounting surface for the removable mounting bracket that will allow the

monitored conductor to pass through the center window when it is installed and
that will keep the product at least ½” (13 mm) from any uninsulated conductors.
Determine cable routing for the controller connection, allowing wiring to reach
the mounting location.

2. Drill holes to mount the bracket to the chosen surface using the included screws.

3. Wire the output connections between the sensor and the controller (solid-state

contact).

4. Snap the sensor over the wire to be monitored clip the assembly to the mounting

bracket.

5. Secure the enclosure and reconnect power.