current monit

oring

VERIS INDUSTRIES

800.354.8556

+1 503.598.4564

www.veris.com

Status And Control In One Package

Current Switches with Relay:

Adjustable Trip Point, High

Voltage Output

DESCRIPTION

Hawkeye Relay Combination Series high voltage output current switches are the

ideal solution for the automation installer. These units combine a current switch

and relay into a single package, reducing the space required for total control of fans

and pumps. The integrated current switch and relay operate independently of one

another. All relay connections are externally available for maximum flexibility.

These products perform the functions of start/stop and status monitoring with one

device instead of two.

APPLICATIONS

Starting/stopping and monitoring positive status of motors

Detecting belt loss and coupling shear

FEATURES

Combines command relay & fan/pump status sensor in a single, easy to

install unit

Reduces number of components installed...fits better in small starter enclosures

Command relay and status in a single unit

Easier to install than differential pressure switches...no additional wiring

needed

Detect belt loss and motor failure...ideal for fan and pump status

Bracket on H939, H949, and H959 can be installed in three different

configurations...added flexibility

H749 and H949 feature SPDT command relay...saves installation time

Reduced charges from electrician

Relay and status LEDs for easy setup

Polarity insensitive status output...fast trouble-free installation

Adjustable trip point for current sensor status...fits many applications

5-year warranty

Maximize Reliability

Minimize Installed Cost

SPECIFICATIONS

Sensor Power

Induced from monitored conductor

Insulation Class

600VAC RMS

Frequency Range

50/60 Hz

Temperature Range

-15° to 60°C (5° to 140°F)

Humidity Range

10-90% RH non-condensing

Hysteresis

10% Typical

Terminal Block Wire Size

24-14 AWG (0.2 to 2.1 mm

2

)

Terminal Block Torque

3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)

Agency Approvals

UL 508 open device listing

Do not use the LED status indicators as evidence of applied voltage.

Year

Warranty

5

Voltage

AC

DC

24V................................... 10mA

10mA

12V.................................................................... 20mA

TYPICAL COIL PERFORMANCE

Hx39, Hx59 (SPST, N.O.)
Resistive
................................. 10A@250VAC, 30VDC
Inductive................................ 5A@250VAC, 30VDC
Hx49 (SPDT)
Resistive..............................
8A@250VAC, 30VDC
Inductive............................. 3.5A@250VAC, 30VDC

RELAY CONTACT RATINGS

Pull In Voltage
Hx39 .............................................................. 20.1VDC
Hx49 .............................................................. 20.1VDC
Hx59 .............................................................. 8.4VDC
Drop Out Voltage
Hx39 .............................................................. 5.2VDC
Hx49 .............................................................. 5.2VDC
Hx59 .............................................................. 3.0VDC

H739

H939

H739 SERIES & H939 SERIES

TM

DETECTS BELT LOSS/COUPLING SHEAR!

DETECTS BELT LOSS/COUPLING SHEAR!

Now you can easily detect when drive belts slip, break, or pump couplings shear.

In fact, a typical HVAC motor that loses its load has a reduction of current draw

of up to 50%. That’s why our sensors are the industry standard for status.

Calibrated

Trip Point

Off

Off

Fan/pump

On

Loss of Belt/Coupling Shear

Electrical

Failure

HQ0001761.C 01131