Veris Industries PW2 SERIES Install User Manual

Pw2 series, Notice, Wet media differential pressure transducer

Advertising
background image

VERIS INDUSTRIES

environmental SenSorS

inStallation GUiDe

Z204201-0G

PAGE 1

©2010 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

08102

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

Wet Media Differential Pressure Transducer

quick install

Installer's Specifications

PW2 SerieS

PW2 SerieS

Dimensions

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.
• Read and understand the instructions before installing
this product.
• Turn off all power supplying equipment before working on it.

• The installer is responsible for conformance to all applicable codes.

ProDuct iDentification

Mount sensor on a duct or pipe, across the pump, filter, or other pressure

1.

differential.

Wire as shown (see page 2).

2.

Configure the jumpers (see page 2).

3.

Media Compatibility

17-4 PH stainless steel

Input Power

12 to 24VDC, 29mA max.; loop powered

Output

2-wire transmitter; 4-20mA (clipped and capped)

Pressure Ranges:

0-50 psi (0-3.45 bar)

5/10/25/50 psid (0-0.34/0.69/1.72/3.45 bar)

0-100 psi (0-6.89 bar)

10/20/50/100 psid (0-0.69/1.38/3.45/6.89 bar)

0-250 (0-17.24 bar)

25/50/125/250 psid (0-1.72/3.45/8.62/17.24 bar)

Proof Pressure

2x max. F.S. range

Burst Pressure

5x max. F.S. range

Accuracy at 25°C*

Ranges A, B, C: ±1% F.S.**

Range D: ±2% F.S.**

Surge Damping

Electronic; 5-second averaging

Temperature Compensated Range

0° to 50°C (32° to 122°F);

TC Zero <1.5% of product F.S. per sensor;

TC Span <1.5% of product F.S. per sensor

Sensor Operating Range

-20° to 85°C (-4° to 185°F)

Long Term Stability

±0.25% per year

Zero Adjust

Pushbutton auto-zero

Operating Environment

-10° to 55°C (14° to 131°F); 10-90% RH noncondensing

Fittings

1/8” NPT female, stainless steel 17-4 PH

Physical

White powder-coated aluminum

To conform to EMC Standards, use shielded cabling. Technical information is available from the

factory on request or on our website (www.veris.com/ce)

* Accuracy combines linearity, hysteresis, and repeatability.

** F.S. is defined as full span of selected range in bidirectional mode.

2.2"

(57 mm)

4"

(102 mm)

5.8"

(147 mm)

LOW

HIGH

WET DIFFERENTIAL PRESSURE

The PW2 Series sensor is designed to accept high differential pressure. Install the
sensor on a duct or pipe across a pump, filter, heat exchanger, compressor, or other
non-corrosive wet media. The dual sensor design eliminates the need for a bypass
valve, and the bi-directional capability reduces installation errors. A pushbutton
allows easy zero adjustment.

Local Display

L = LCD Display
X = No Display

NIST

N = NIST
X = None

US or EU

S = Standard
C = CE

Operational Range

03 = 0-50 psig
04 = 0-100 psig
05 = 0-250 psig

PW2

*

* IMPORTANT!
Select operational range according to maximum gauge pressure, NOT differential pressure.
Example: High gauge pressure=90 psig, Select 100 psig model (04).

available