SPECIFICATIONS

Sensor Power

Induced from monitored conductor

Response Time

1 sec.

Accuracy

±2% of full scale

Frequency Range

50/60 Hz

Temperature Range

-15° to 60°C (5° to 140°F)

Humidity Range

10-90% RH non-condensing

LCD Backlight

Off at low currents; illuminates when monitored current exceeds 4.5A;

flashes during an alarm state while current remains above 4.5A

On-State Resistance

≤1.0 Ω

Off-State Resistance

≥1.0 MΩ

Setpoint Target Range, Switch Setting A*

±40% of learned nominal current; max. learned current of 142A to enable an upper trip limit at or below 200A

Setpoint Target Range, Switch Setting B*

±60% of learned nominal current;max. learned current of 125A to enable an upper trip limit at or below 200A

Switch Setting C*

On/Off Status; contacts are closed while amperage is above 2.5A

Alarm Reset Range

±5% of learned nominal current **

Setpoint Calibration Learn Period

30 sec.; self-learning, pushbutton reset

Normal-to-Alarm Output Delay

1 sec. maximum

Alarm-to-Normal Output Delay

30 sec. nominal

Insulation Class

600VAC RMS (UL); 300VAC RMS (CE)

Terminal Block Wire Size

24-14 AWG (0.2 to 2.1 mm

2

)

Terminal Block Torque

3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)

Agency Approvals

UL508 open device, CE: EN61010-1:2001-02, CAT III, pollution degree 2

* Trip point switch positions A and B are not for use in applications where the current will fluctuate by more than 40% (A) or 60% (B) of the nominal current. If the current will fluctuate by more than 60%, use the H11D for on/

off status (position C) only.

** The upper trip limit alarm resets when the current drops by 5% of the learned nominal current limit. The lower trip limit alarm resets when the current rises by 5% of learned nominal current limit.

Specification Note: For CE compliance, conductor shall be insulated according to IEC 61010‑1:2001.

The product design provides for basic insulation only.

Do not use the LCD as evidence of applied voltage.

DESCRIPTION

The Hawkeye TruStat H11D is a microprocessor based, self-learning, self-calibrating

current switch. It is designed for user ease, providing calibration-free status for

both under and overcurrent, an LCD display, and slide-switch selectable trip point

limits. At initial power-up, the H11D automatically learns the average current on the

line with no action required by the installer. Once a current is learned, the switch

monitors for changes in current greater than the selected range.

APPLICATIONS

HVAC fans, pumps, and blowers

Monitoring status of industrial process equipment

FEATURES

Backlit LCD display...view the monitored current (up to 200A)...eliminates the

need for expensive handheld meters and offers easy visibility in dark enclosures

Automatic calibration...reduced errors and installation costs

Slide-switch selectable trip point limits...application versatility

Microcontroller based learning technology...automatically learns load upon

initial power-up...eliminates labor associated with calibration

Records and displays the amperage level that trips the alarm...simplifies

troubleshooting

Reset function can be used when unpowered...reduces the possibility of an

undesirable arc flash incident

Monitors current for both under- and over-load in one package

100% solid state...no moving parts to fail

Small size fits easily inside small starter enclosures...saves space

Self-gripping iris for easy installation

Bracket can be installed in three different configurations...added flexibility

5-year warranty

LCD Display

Current Switch:

Auto Calibration,

Automation Systems

Maximize Reliability

Minimize Installed Cost

Year

Warranty

5

H11D

H11D

TM

LCD

DISPLA

Y!

LCD

DISPLA

Y!

HQ0003679.C 01131

Advertising