Z203538-0F

PAGE 4

©2011 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

07111

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

TM

H8920-3

INSTALLATION GUIDE

Indexing Option: Allows the node to access up to 63 H8163 meters for

viewing and archiving purposes only

NETWORK OPTIONS

Bound Option: For all applications requiring binding*

H8920-3

LON Node

H8163 with

H8163-CB installed

H8163 with

H8163-CB installed

Modbus Network

LON Talk® Network

Lon Talk®

Controller

*If employing the bound option, address each H8163-CB at 1.

Node Identification

Wink: The LON Node will light its service LED for 5 seconds in response to a WINK
command.

Service Pin: A service pushbutton is provided for this method of identification.
(See Product Diagram section).

Neuron ID: The Neuron ID is located on a label on the back of the device. It can be
written down or peeled off as a removable sticker with bar code for easy insertion to
your network.

Program ID

The standard program ID for this product is 90:00:14:8A:0F:02:04:01

Up to 63 H8163 meters with H8163-CB installed

H8920-3 LON Node

LON Talk® Network

Modbus Network

Lon Talk®

Controller