Object_Name

Description

R/W

NV

Units

Range

Additional information

AI26

kVAh

Apparent Energy

Consumption

R

NV

kVAh

0 - 3.4+E38

The UNITS property of object AI26 reports that these units

are kWh because there is no unit type in the BACnet

standard for kVAh.

AI27

kVARh

Reactive Energy

Consumption

R

NV

kVARh

0 - 3.4+E38

The UNITS property of object AI27 reports that these units

are kWh because there is no unit type in the BACnet

standard for kVARh.

AI28

kVA_A

Apparent Power

Phase A

R

kVA

0 - Max_Power (AI45)

AI29

kVA_B

Apparent Power

Phase B

R

kVA

0 - Max_Power (AI45)

AI30

kVA_C

Apparent Power

Phase C

R

kVA

0 - Max_Power (AI45)

AI31

KVAR_A

Reactive Power

Phase A

R

kVAR

0 - Max_Power (AI45)

AI32

KVAR_B

Reactive Power

Phase B

R

kVAR

0 - Max_Power (AI45)

AI33

KVAR_C

Reactive Power

Phase C

R

kVAR

0 - Max_Power (AI45)

AI34

KW_Present_

Demand

Total Real Power

Present Demand

R

kW

0 - Max_Power (AI45)

AI35

KVAR_Present_

Demand

Total Reactive Power

Present Demand

R

kVAR

0 - Max_Power (AI45)

AI36

KVA_Present_

Demand

Total Apparent Power

Present Demand

R

kVA

0 - Max_Power (AI45)

AI37

KW_Max_

Demand

Total Real Power

Maximum Demand

R

NV

kW

0 - Max_Power (AI45)

This retains the largest value measured for Total Real

Power Demand (AI34) for any single demand interval

since the Max Demand was last explicitly reset via

AV1 (this is also reset when the demand interval is

changed).

AI38

KVAR_Max_

Demand

Total Reactive Power

Maximum Demand

R

NV

kVAR

0 - Max_Power (AI45)

This retains the largest value measured for Total Reactive

Power Demand (AI35) for any single demand interval

since the Max Demand was last explicitly reset via

AV1 (this is also reset when the demand interval is

changed).

AI39

KVA_Max_

Demand

Total Apparent Power

Maximum Demand

R

NV

kVA

0 - Max_Power (AI45)

This retains the largest value measured for Total Apparent

Power Demand (AI36) for any single demand interval

since the Max Demand was last explicitly reset via

AV1 (this is also reset when the demand interval is

changed).

AI40

E50H2: Pulse

Count

E50H5: Pulse_

Count_1

E50H2: Pulse Count
E50H5: Pulse Count

#1

R

NV

#

0 - 4294967040

Running count of contact closures on Pulse1 input since

last reset. Write 16498 (0x4072) to the Present_Value

property of Analog_Value object AV1 to reset both

Pulse Counters to 0.

AI41

E50H2: Reserved
E50H5: Pulse_

Count_2

E50H2: Reserved
E50H5: Pulse Count

#2

R

NV

#

0 - 4294967040

E50H2: Reserved
E50H5: Pulse Count 2; Running count of contact closures

on Pulse2 input since last reset. Write 16498 (0x4072)

to the Present_Value property of Analog_Value object

AV1 to reset both Pulse Counters to 0.

AI42

KWH_A

Real Energy

Consumption

Phase A

R

NV

kWh

0 - 3.4+E38

AI43

KWH_B

Real Energy

Consumption

Phase B

R

NV

kWh

0 - 3.4+E38