CURRENT MONITORING

INSTALLATION GUIDE

Split-Core Current Switch,

Fixed Trip Point

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

• Follow safe electrical work practices.

See NFPA 70E in the USA, or applicable local codes.

• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.

Failure to follow these instructions will result in death or serious injury.

DANGER

WIRING EXAMPLE

H800HV

TM

800HV

DIMENSIONS

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.

• The installer is responsible for conformance to all applicable codes.

• Mount this product inside a suitable fire and electrical enclosure.

INSTALLATION

Disconnect and lock out power to the enclosure containing the

conductor to be monitored.

1. Locate a mounting surface for the removable mounting bracket that will allow

the monitored conductor to pass through the center window when it is installed
and that will keep the device at least 1/2” from any uninsulated conductors.
Determine cable routing for the output connection, allowing wiring to reach the
mounting location.

2. Drill holes to mount the bracket to the chosen surface using the included screws.

3. Wire the output connections and relay between the sensor and the controller

(solid-state contact) and external power supply.

4. Route the conductor through the sensor’s center window and slip the assembly

into the mounting bracket.

5. Secure enclosure and reconnect power.

ø 0.7"

(18 mm)

0.4” x 0.2”

Slot (x2)

2.8" *

(71 mm)

1.7

(43 mm)

2.3"

(58 mm)

1.1" *

(27 mm)

0.9"

(23 mm)

Removable/Adjustable Mounting Bracket

POWER

SOURCE

POWER

SOURCE

BUILDING AUTOMATION

CONTROLLER

UNIT VENT HEATER

DI

DI

Installer’s Specifications

Sensor Power

Induced from monitored current

Insulation Class

600VAC RMS (UL)

Frequency Range

50/60 Hz

Temperature Range

-40° to 50°C (-40° to 122°F) (to 200A);

-40°

to 75°C (-40° to 167°F) (to 100A & 0.25A output)

Humidity Range

10-90% RH, non-condensing

Output

N.O. 500mA@250VAC/DC, polarity insensitive

Amperage Range

0.75-200A Continuous

Terminal Block Maximum Wire Size

14 AWG

Terminal Block Torque (nominal)

4 in-lbs (0.45 N-m)

Agency Approvals

UL 508 open device listing

The product design provides for basic insulation only.