INSTALLATION GUIDE

Temperature Range Configuration

AA10

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.

• Read and understand the instructions before installing

this product.

• Turn off all power supplying equipment before working on it.

• The installer is responsible for conformance to all applicable codes.

No responsibility is assumed by Veris Industries for any consequences arising out of the

use of this material.

DIMENSIONS

AA10

PRODUCT IDENTIFICATION

°C

°F

Order Code

-50 to 50

-58 to 122

1

0 to 50

32 to 122

2

0 to 100

32 to 212

3

10 to 35

50 to 95

4

0 to 150

32 to 302

5

-18 to 38

0 to 100

6

-18 to 121

0 to 250

7

-18 to 66

0 to 150

8

-29 to 66

-20 to 150

9

-60 to 70

-76 to 158

10

0 to 66

32 to 150

11

Example:

AA10C3

1.3”

(32mm)
nominal

1.5” (39mm)

1.0” (26mm)

INSTALLATION

1. Disconnect power to the control panel.

2. Wire the AA10 as shown in the Wiring section. For a 1-5 VDC output, use a 250 Ω

resistor (not included).

3. Refer to the Product Identification chart to determine the output temperature

range scaling.

SPECIFICATIONS

Transmitter:

Input Voltage

12 to 24VDC

Loop Resistance 250

Ω, 13.5V min.; 500 Ω, 18.5V min.

Output

4-20mA, 2-wire, loop powered; 1-5VDC with 250 Ω resistor

Transmitter Accuracy

±2.5% of span (typical)

Adjustment

±5% zero and span

Ambient Temperature 0° to 50°C (32° to 122°F)

Encapsulation

Epoxy encapsulated

Sensor (sold separately):

Sensor Type

RTD, Platinum, 100 Ω, 0.0385

α

Sensor Accuracy

±0.30°C

Conversion Resistor 250Ω min. ¼ watt

WIRING

Current Output

POWER SUPPLY

12 to 24 VDC

DIGITAL CONTROL

RTD

Temperature

4-20 mA return

+

+

Voltage Output

POWER SUPPLY

12 to 24 VDC

DIGITAL CONTROL

RTD

Temperature

1-5VDC return

+

250Ω

+

AA10SPC01363
AA10SPC01365
AA10SPC01366

°C

°F

-7 to 49

20 to 120

0 to 30

32 to 86

-10 to 10

14 to 50

PRODUCT OVERVIEW

The AA10 is intended for use with a 100 Ω platinum RTD (0.0385

α) to provide either a

4-20 mA or a 1-5 VDC temperature signal.

Advertising