INSTALLATION GUIDE

ENERCEPT

TM

H8051/H8053

Pulse Output kWh Transducers

QUICK INSTALL

Disconnect and lock out power to the enclosure containing the

conductor before installation.

1. Set the pulse rate switches located on the bottom of the CT(s).

2. Connect the voltage leads to the source to be monitored.

3. Snap the CT(s) onto the conductor (observe color matching).

4. Connect the pulse output wires (observe polarity).

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

• Follow safe electrical work practices.

See NFPA 70E in the USA, or applicable local codes.

• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.

Failure to follow these instructions will result in death or serious injury.

DANGER

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.

• The installer is responsible for conformance to all applicable codes.

• Mount this product inside a suitable fire and electrical enclosure.

FCC PART 15 INFORMATION
NOTE: This equipment has been tested by the manufacturer and found

to comply with the limits for a class A digital device, pursuant to part
15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference when the equipment is
operated in a commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if not installed and
used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in
a residential area is likely to cause harmful interference in which case
the user will be required to correct the interference at his own expense.
Modifications to this product without the express authorization of
Veris Industries nullify this statement.

CAUTION

RISK OF EQUIPMENT DAMAGE

Enercept meters are rated for use at 50-60Hz. Do not connect this product to circuits with

high harmonic energy, such as Variable Speed Drives (a.k.a. Variable Frequency Drives,

Adjustable Frequency Drives) or similar sources, as these may permanently damage the

product.

Failure to follow these instructions can result in overheating and permanent

equipment damage.

IND. CONT. EQ.

UL 508

US Patent No. 6,373,238

For use in a Pollution Degree 2 or better environment only. A Pollution Degree 2 environment must
control conductive pollution and the possibility of condensation or high humidity. Consider the
enclosure, the correct use of ventilation, thermal properties of the equipment, and the relationship
with the environment. Installation category: CAT II or CAT III

Installer’s Specifications

Measurement Accuracy:

System Accuracy

±1% of reading from 10% to 100% of the rated current*

Type of Measurement

One or three phase AC system

Input Voltage Characteristics:

Measured AC Voltage

208-480 VAC

Frequency Range

50/60 Hz

Fuses

1/2A, 600VAC, 200 kAIC

Input Current Characteristics:

Maximum Primary Current

100, 300, 400, 800, 1600, or 2400A**

Meter Current Draw:

Maximum

60mA AC

Output:

Pulse

N.O. Opto-Fet

Max. Pulse Output Current

100mA@24VAC/DC

Field Selectable Pulse Rate

1, 0.5, 0.25, or 0.1 kWh/pulse

Pulse Width

200 msec

Mechanical Conditions:

CT Case Isolation

600VAC

Internal Isolation

2000VAC RMS

Environmental Conditions:

Operating Temperature Range

0° to 60°C (32° to 140°F)

Storage Temperature Range

-40° to 70°C (-40° to 158°F)

Operating Humidity Range

<95% RH non-condensing

Safety:

US and Canada (cULus)

UL508 (open type device)

* Meter accuracy specified with conductors centered in the CT window.