Zone Leak Detection Controller

Zone Leak

Detection Panels

DESCRIPTION

LD300, LD1000, and LDRA6 control panels continuously monitor up to 1,000 ft.

(300 ft. for the LD300) of SC, SC-Con, or SC-H detection cable per zone. If the cable

detects fluid at any point along its length, the detection panel illuminates the

corresponding zone LED, clearly indicating which zone is affected. An alarm (visual

for LD300, audible for all others) signals the presence of a leak. Additionally, if the

cable fails or loses continuity, the panel will activate a cable fault LED. The detection

sensitivity can be set independently for each zone. A summary alarm relay output is

standard.

The LDRA6 can interface with a computer via an RS-232 port, through which 117

days of cable current level readings and the last 100 alarms can be accessed for

analysis. The LDRA6 also offers a Modbus slave port allowing other devices to

communicate with it.

APPLICATIONS

Monitoring data centers, computer room under-floor areas, mechanical rooms,

and electrical control centers

Protecting records storage rooms

Monitoring plumbing in facilities

Monitoring chilled beams

Monitoring chemical and fuel storage areas

FEATURES

Monitor up to 1,000 ft. (300 m) of water leak detection cable per zone with the

LD100 and LDRA6 or 300 ft. per zone with the LD300...application flexibility

Two LED indicators per zone...leak and cable fault (LD1000 and LDRA6)

Sensitivity settings for each zone help eliminate false alarms...maximum

detection accuracy

Summary alarm relay output...fast response

Alarm and trend logs of the last 100 alarms and 117 days of cable current levels,

plus RS-232 and Modbus RS-485 ports (LDRA6 only)...output versatility

SPECIFICATIONS

Input Power

LD300: 5VDC ±10%; LD1000: 24VAC/DC (±10%)@300mA max.; LDRA6: 24VAC/DC (±10%)@600mA max.

Inputs:

Water Leak Detection Cable

Requires 15 ft. (4.5 m) leader cable kit (LC-Kit) per zone

Maximum Cable Length

LD300: 300 ft. (91 m); LD1000, LDRA6: 1000 ft. (305 m)

Detection Response Time

LD300: < 20 sec (10 sec typical); LD1000: Configurable for 10 sec or 2 min, ± 10%

LDRA6: 20-3600 sec, software adjustable in 10 sec increments, ± 2%

Relay Output

LD300: 2 Form C relays (leak and fault); 1A@24VDC, 0.5A resistive@120VAC; LD1000: 2 Form C relays (leak and fault); 1A@24VDC, 0.5A resistive@120VAC

LDRA6: 1 Form C summary alarm relay, 1 Form C relay for each zone/alarm; 1A@24VDC, 0.5A resistive@120VAC

Communication Ports (LDRA6 only):

RS-232 & RS-485

1200, 2400, 9600, or 19200 selectable; no parity; 8 data bits, 1 stop bit

Terminal Emulation (RS-232)

VT100 Compatible (configuration)

Modbus (RS-485) (LDRA6 only)

Slave; RTU Mode; Supports function codes 03, 04, 06 and 16

Alarm Notification Audible Alarm

LD1000: 85 dBA@2 ft. (0.6 m); LDRA6: 85dBA@2 ft. (0.6 m) re-sound disabled, 8, 16, or 24 hrs.

Push Buttons

LD1000, LDRA6: 1 for reset, quiet, and test

Operating Environment:

Temperature

0° to 50°C (32° to 122°F)

Humidity

5% to 95% RH non-condensing

Altitude

15,000 ft. (4,572 m) max

Storage Environment

-20° to 70°C (-4° to 158°F)

Weight

LD300: 3 oz. (85 g); LD1000: 27 oz. (766 g); LDRA6: 4 lbs. (2 kg)

Agency Approvals

LD300: CE, RoHS compliant; LD1000: CE, ETL listed; conforms to UL 61010-1, RoHS compliant

LDRA6: CE; ETL Listed; conforms to UL 61010-1, EN 61010-1, CAN/CSA C22.2 No. 1010.1, RoHS compliant

LD1000

LDRA6

LD300

LD300, LD1000, & LDRA6

HQ0001795.B 01131