Veris Industries HED SERIES Install User Manual

Hed series, Notice, Economy duct mounted humidity sensor

Advertising
background image

Z205848-0C

PAGE 1

©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

07122

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

TM

EnvironmEntal SEnSorS

inStallation GUiDE

Economy Duct Mounted Humidity Sensor

Installer’s Specifications

Input Power:

Input Power, Voltage Version

12-24 VDC or 24 VAC

Input Power, mA Version

12-24 VDC

AC Voltage Tolerance

±10%

AC Frequency

50-60 Hz

Max. Inrush Current After 1 msec (mA version)

25 mA

Output Power:

mA Output

4-20 mA, 2-wire, polarity insensitive

mA Max. Loop Resistance

500 Ω at 24 VDC input voltage; 250 Ω at 12 VDC input voltage

Voltage Output

0-5 V or 0-10 V (jumper selectable)

Voltage Min. Load Resistance

5 kΩ

Voltage Min. Sinking Current

0.2 mA

Humidity:

HS Element

Digitally profiled thin-film capacitive, non-removable

Accuracy

±2%, 3% or 5% (10-90% RH, 20° to 30°C)

Temperature Effect (Outside 20° to 30°C)

≤0.1% RH per °C

Response Time (to 90% change at 20°C)

110 sec

Annual Drift ≤1%

Output Scaling

0-100% RH

Temperature:

Active Output Accuracy

±0.5°C

Active Output Temperature Scaling

Type 1: -40° to 50°C (-40° to 122°F)

Type

2: 0° to 50°C (32° to 122°F)

Resistive Temperature Accuracy

see thermistor table

Self-Heating Error (Resistive temperature only)

≤±0.5°C at 20° to 30°C;

≤±0.75°C

outside of 20° to 30°C

Operating Environment:

Operating Temperature

-40° to 50°C

Operating Humidity

0-100% RH (non-condensing) (Unit will recover from saturation)

Housing:

Material

ABS plastic with UL V-0, 5VA Flame Class

EMC Conformance: EN61000-6-3:2007 +A1:2011 Class B, EN61326-1:2006 Class B;

EN61000-6-1:2007

Meets UL requirements for plenum rating.

1-year limited warranty.

HED SEriES

HED SEriES

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.
• Read and understand the instructions before installing
this product.
• Turn off all power supplying equipment before working on it.

• The installer is responsible for conformance to all applicable codes.

Product IdentIfIcatIon

quIck Install

Observe precautions for handling static sensitive

devices to avoid damage to the circuitry that

is not covered under the factory warranty.

1. Choose a location on the air duct.

2. Drill a 1” (25 mm) diameter hole for the sensor probe.

3. Mount HED housing to duct using self-tapping screws (included).

4. Wire unit (see Wiring section).

HED

T = Temp
X = No Temp
(Stop here)

S

= Standard

Output

Temp.

Sensor Type

Accuracy

Temp Cert

Blank = None
1 = 1 pt cal
2 = 2 pt cal

Sensor Type

= Temp. transmitter

A

Temp Range

1 = -40° to 50°C (-40° to 122°F)
2 = 0° to 50°C (32° to 122°F)

Temp Cert

Blank = None
1 = 1 pt cal
2 = 2 pt cal

OR

RoHS

Compliant

M = 4-20mA
V = 0-5V/0-10V

B = 100R Platinum, RTD
C = 1k Platinum, RTD
D = 10k T2, Thermistor
E = 2.2k, Thermistor
F = 3k, Thermistor
G = 10k CPC Thermistor
H = 10k T3, Thermistor
J = 10k Dale, Thermistor
K = 10k with 11k shunt, Thermistor
M = 20k NTC, Thermistor

N = 1800 ohm TAC, Thermistor
R = 10k US, Thermistor
S = 10k 3A 221 Thermistor
T = 100k, Thermistor
U = 20k “D”, Thermistor
W = 10k T2 high accuracy, Thermis-
tor
Y = 10k T3 high accuracy, Thermistor
Z = 10k E1, Thermistor

2 = 2%
3 = 3%
5 = 5%