Veris Industries H908 Install User Manual

H908, Current monitoring, Installation guide

Advertising
background image

Installation Guide

Current Monitoring

Z201494-0F

Page 1 of 4

©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 06132

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

TM

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

• Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.

Failure to follow these instructions will result in death or serious injury.

A qualified person is one who has skills and knowledge related to the construction and

operation of this electrical equipment and the installation, and has received safety

training to recognize and avoid the hazards involved.

NEC2009 Article 100

No responsibility is assumed by Veris Industries for any consequences arising out of the

use of this material.

DANGER

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.

• The installer is responsible for conformance to all applicable codes.

• Mount this product inside a suitable fire and electrical enclosure.

Product Overview

The H908 is a current-sensitive switching device that monitors current (amperage) in the conductor passing
through it. A change in amperage in the monitored conductor that crosses the switch (setpoint) threshold plus the
hysteresis value causes the resistance of the FET status output to change state, similar to the action of a mechanical
switch. In this model, the setpoint is adjustable through the action of a twenty (20) turn potentiometer (see the
CALIBRATION section). The status output is suitable for connection to building controllers or other appropriate data
acquisition equipment operating at up to 30 volts. The H908 requires no external power supply to generate its
output.

The H908 housing offers unprecedented mounting flexibility. The mounting bracket can be attached in three
different places. Additionally, the bracket is compatible with the Veris AH01 DIN Rail clip, allowing DIN mounting.

H908

Split-Core Current Switch, Adjustable Trip Point

Specifications

Sensor Power Induced from the monitored conductor

Amperage Range 2.5 to 135 A continuous

Status Output Ratings N.O. 1.0 A@30 VAC/DC, not polarity sensitive

Insulation Class 600 VAC RMS (UL); 300 VAC (CE)

Setpoint Adjustable, 2.5 A or less

Frequency Range 50/60 Hz

Temperature Range -15° to 60°C (5° to 140°F)

Humidity Range 10-90% RH non-condensing

Hysteresis 10% typical

Off State Resistance Open switch represents >1 MΩ

On State Resistance Closed switch represents < 200 mΩ

Terminal Block Wire Size 24 to 14 AWG (0.2 to 2.1 mm

2

)

Terminal Block Torque 3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)

COMPLIANCE INFORMATION

Agency Approvals UL508 open device listing, CE: EN61010-1

Installation Category Cat. III, pollution degree 2

For applications requiring double or reinforced insulation, please contact the factory.

The product design provides basic insulation only.

Do not use the LED indicators as evidence of applied voltage.

TM

RoHS

Compliant