Veris Industries H932 Datasheet User Manual

Current sensors with relay: 0-5vdc analog output, Load trending and control relay in one package, Current monit oring

Advertising
background image

current monit

oring

VERIS INDUSTRIES

800.354.8556

+1 503.598.4564

www.veris.com

DESCRIPTION

The Hawkeye 932 and H952 Series provide accurate load trending information

with a proportional 0-5VDC output signal. This feature combined with an integrated

command relay makes these products ideal for start/stop and status monitoring

of motors.

The relay is fully isolated from the current sensor, and all relay connections are

externally available for maximum flexibility.

APPLICATIONS

Load trending

Motor control

Fan/Pump status

FEATURES

Self-powered analog current sensor with integral start/stop command relay

Reduces the number of installed components... saves time and space

Self-gripping split-core for fast retrofit installation...no need to remove

conductor

One device to install for start/stop and status...reduces installation charges

No external power required for current sensor

Selectable factory calibrated ranges up to 120A for increased flexibility

and resolution

Factory calibrated switch-selectable ranges (30/60/120A) for high resolution

and installation ease

No jumpers on unit...reduces installation error

Removable mounting bracket for installation flexibility

Bracket can be installed in three different configurations...added flexibility

Command relay switches up to 5A@250VAC

5-year warranty

SENSED AMPS

30/60/120A*

0V

0A

5V

SENSOR OUTPUT

*Factory calibrated ranges selected

with the amperage range switch

Load Trending And Control

Relay In One Package

H932/952 LINEAR OUTPUT

Scale software as shown

Maximize Reliability

Minimize Installed Cost

SPECIFICATIONS

Sensor Power

Induced from monitored conductor

Insulation Class

600VAC RMS

Frequency Range

50/60 Hz nominal

Temperature Range

-15° to 60°C (5° to 140°F)

Humidity Range

10-90% RH non-condensing

Accuracy

±2% F.S. from 10% to 100% (selected range)

Response Time

2 sec.

Terminal Block Wire Size

24-14 AWG (0.2 to 2.1 mm

2

)

Terminal Block Torque

3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)

Agency Approvals

UL 508 open device listing; CE: EN61010-1:2001-2, CAT III, pollution degree 2, basic insulation

Current Sensors with Relay:

0-5VDC Analog Output

Year

Warranty

5

H932

H932 & H952

TM

HQ0001767.B 01131

Advertising