Veris Industries 3x0 SERIES Datasheet User Manual

3x0 series, Fl ow

Advertising
background image

fl

ow

VERIS INDUSTRIES

800.354.8556

+1 503.598.4564

www.veris.com

Transmitter: Analog, BTU,

Pulse and Protocol Output

DESCRIPTION

3x0 programmable transmitters are capable of converting the frequency signal from

any of our flow sensors to a preferred output type (analog, scaled pulse, protocol).

In addition to standard square wave signals, it can also accept a sine wave, making

it a versatile transmitter for numerous applications. The 310 and 320 offer analog

and scaled pulse output, respectively, while the 340 models offer communication

protocols (N2, BACnet/Modbus, or LonWorks), with energy (BTU) measurement

(appropriate software and programming cables are required for installation; see

Ordering Information).

APPLICATIONS

Converting sine/square wave signals to 4-20 mA and protocol

Increasing wire run length limit for flow sensors

Connecting flow sensors to BAS panels

FEATURES

Programmable (units of measure, calibration, etc.) using computer with

Windows-based operating system...save installation time in the field by

pre-programming the device

Accepts sine wave input from a variety of other sources for application

flexibility

Compact size...saves space in crowded enclusures

Communication protocols available on the 340 models

310 SPECIFICATIONS

Power Requirements

Loop input voltage 9-35VDC

Input Frequency

0.4 Hz to 10 kHz

Load Resistance

Max 750Ω@24VDC

Operating Temperature Range

-29° to 70°C (-20° to 158°F)

Storage Temperature Range

-40° to 85°C (-40° to 185°F)

Accuracy

±0.04% of reading over entire span

Linearity

0.1% of full scale

320 SPECIFICATIONS

Power Requirements

12-30VACm 85mA max.; 12-40VDC, 30mA max.; Reverse and over voltage protected to 40VDC

Input Frequency

0.4 to 10 kHz

Transient Suppression

Complies with IEC-801-4 electrical burst, fast transient specification

Pulse Output

Isolated solid state switch in any standard or custom flow total units; Adjustable 50 msec to 1.0 sec pulse output width in 50 msec increments

Maximum Sinking Current 100mA@36VDC

Operating Temperature Range

-29° to 70°C (-20° to 158°F)

Storage Temperature Range

-40° to 85°C (-40° to 185°F)

340 SPECIFICATIONS

Power Requirements

12-24VDC or 12-24VAC, 70mA max.

Flow Sensor Input

Excitation voltage 3-wire sensors: 9.1VDC 500Ω source impedance

Frequency

4-10000 Hz

Temperature Sensor Input

10k Dale Thermistor (requires 2, sold separately)

Operating Temperature Range

-29° to 70°C (-20° to 158°F)

Storage Temperature Range

-40° to 85°C (-40° to 185°F)

Units of Measure:

Flow Rate

gpm, gph, l/sec, l/min, l/hr, ft3/sec, ft3/min, ft3/hr, m3/sec, m3/min, m3/hr

Total Flow

gallons, liters, cubic feet, cubic meters

Energy Rate

kBTU/min, kBTU/hr, kW, MW, hp, tons

Total Energy

BTU, kBTU, MBTU, kWh, MWh, kJ, MJ

Converts Flow Signal To A

Linear 4-20mA Analog or

a Protocol Signal

310-00

Year

Warranty

1

320-00

340-00

NEW!

both bacne

t

& modbus i

n

one btu

transmitte

r

3x0 SERIES

HQ0001785.D 01131

Advertising