Veris Industries H970HCB Install User Manual

Installation guide, Wiring example, Dimensions

Advertising
background image

6%2)3

CURRENT MONITORING

INSTALLATION GUIDE

Z203257-0D

PAGE 1

©2009 Veris Industries USA 800.354.8556 or +1(0)503.598.4564 / [email protected]

07091

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

Split-Core Low Current 4-20mA & 0-10 VDC

DC Current Transducer

Installer’s Specifications

Technology

Open loop Hall effect

Amperage Range

0 to 50/100/200 ADC (slide switch selectable)

Sensor Supply Voltage

15 to 30VAC/DC

Supply Current

35mA max.

Isolation

600VAC rms

Temperature Range

-15° to 60°C (5° to 140°F)

Humidity Range

10-90% RH non-condensing

Output

4-20mA and/or 0-10VDC

Accuracy

±3% F.S. combined linearity, hysteresis, and repeatability

The product design provides for basic insulation only.

)";"3%0'&-&$53*$4)0$, &91-04*0/ 03"3$'-"4)

t 'PMMPXTBGFFMFDUSJDBMXPSLQSBDUJDFT

4FF/'1"&JOUIF64" PSBQQMJDBCMFMPDBMDPEFT

t 5IJTFRVJQNFOUNVTUPOMZCFJOTUBMMFEBOETFSWJDFECZRVBMJmFEFMFDUSJDBMQFSTPOOFM
t 3FBE VOEFSTUBOEBOEGPMMPXUIFJOTUSVDUJPOTCFGPSFJOTUBMMJOHUIJTQSPEVDU
t 5VSOPõBMMQPXFSTVQQMZJOHFRVJQNFOUCFGPSFXPSLJOHPOPSJOTJEFUIFFRVJQNFOU
t 6TFBQSPQFSMZSBUFEWPMUBHFTFOTJOHEFWJDFUPDPOmSNQPXFSJTPõ
 %0/05%&1&/%0/5)*4130%6$5'0370-5"(&*/%*$"5*0/
t 0OMZJOTUBMMUIJTQSPEVDUPOJOTVMBUFEDPOEVDUPST

'BJMVSFUPGPMMPXUIFTFJOTUSVDUJPOTXJMMSFTVMUJOEFBUIPSTFSJPVTJOKVSZ

%"/(&3

Wiring ExamplE

H970HCB

970HCB

DimEnsions

/05*$&

t 5IJTQSPEVDUJTOPUJOUFOEFEGPSMJGFPSTBGFUZBQQMJDBUJPOT

t %POPUJOTUBMMUIJTQSPEVDUJOIB[BSEPVTPSDMBTTJmFEMPDBUJPOT

t 5IFJOTUBMMFSJTSFTQPOTJCMFGPSDPOGPSNBODFUPBMMBQQMJDBCMFDPEFT

t .PVOUUIJTQSPEVDUJOTJEFBTVJUBCMFmSFBOEFMFDUSJDBMFODMPTVSF

quick install

Disconnect and lock out power to the conductor to be monitored.

1.

Choose a location for the sensor. The monitored conductor must pass through the

2.

iris, and the sensor must be at least 1/2” from any uninsulated conductors.

Install the adjustable mounting bracket to the back of the enclosure using the

3.

included screws.

Connect 15-30VAC/DC to the terminals marked Power (+) and Gnd (-).

4.

Wire the output (mA or VDC) connections between the sensor and the controller.

5.

Snap the sensor over the conductor to be monitored and clip the assembly to the

6.

mounting bracket.

Set the field-selectable switch to the desired amperage level (see page 2).

7.

Fan or Pump

CONTROLLER

4-20mA DC

Analog

Input

MOTOR

CONTACTOR

Removable Mounting Bracket

Self-gripping

Iris

1.0”

(25 mm)

0.8”

(21 mm)

1.1”

(26 mm)

3.1”

(79 mm)

2.8”

(70 mm)

Ø = 0.3”

(8 mm)

1.4”

(36 mm)

2.5”

(64 mm)

3.0”

(76 mm)

Bracket can be mounted
on either side for added
installation flexibility.

Use DIN Rail

Mounting clip

(Veris part

number AH01) to

mount on stan-

dard DIN rail.