Veris Industries V200 SERIES Datasheet User Manual

Enclosed victory relays: 10a spdt, Great for external mount applications, Year

Advertising
background image

REL

AY

S

VERIS INDUSTRIES

800.354.8556

+1 503.598.4564

www.veris.com

Enclosed Victory Relays:

10A SPDT

DESCRIPTION

Victory 100 and 200 Series 10A enclosed relays are pilot-duty relays in an easy-
to-use nipple mount enclosure. The V100/V200 Series provide quick relay mounting
without a dedicated field enclosure, making them ideal for retrofit projects. Field-
selectable high and low voltage coil inputs provide on-site versatility.

APPLICATIONS

Command contactors

Control motors

Isolation

Device interlocking

Relay logic

Sense voltages for alarm conditions

FEATURES

Sleek field enclosure reduces the need for panel space

The nipple mount feature allows the Victory Series to be mounted to any

electrical enclosure

Flexible tinned stranded wire...fits easily in tight spaces & provides secure

connections to wire nuts

UL508 Listed...designed and approved for field installation...makes electrical

inspection a snap

Run low voltage instead of line voltage...eliminate conduit in some applications

SPECIFICATIONS

Operating Temperature Range:

V100, V100DC, V200

-34° to 60°C (-29° to 140°F)

V100D, V200D

-40° to 55°C (-40° to 131°F)

Operating Humidity Range

10-90% RH non-condensing

Expected Relay Life

Electrical (@ rated current) 100,000 cycles; Mechanical (unpowered) 10,000,000 cycles

Relay Status

LED ON=energized

Wire Specifications:

Lead Length

14” (356 mm) min.

Gauge

UL1015; Coil: 18 AWG; Contacts: 16 AWG

Insulation Class

600VAC RMS

Agency Approvals

UL 508

Great For External

Mount Applications

Pull in Voltage

AC

DC

10-30V..................................... 8

9

120V........................................ 78

208-277V................................. 154
Drop Out Voltage

AC

DC

10-30V..................................... 2 3

120V........................................ 18

208-277V................................ 36
Voltage

Coil Current

AC DC

10V.......................................... 25mA 14mA

12V.......................................... 25mA 14mA

24V.......................................... 31mA 16mA

30V.......................................... 39mA 18mA

120V........................................ 22mA

-

208V........................................ 19mA

277V........................................ 25mA

TYPICAL COIL PERFORMANCE

CONTACT RATINGS

Resistive.............. 10A@277VAC, 28VDC
Motor.................... 120VAC, 1/3HP N.O. & 1/6HP N.C.

240VAC, 1/3HP N.O. & 1/6HP N.C.

277VAC, 1/4HP N.O. & 1/8HP N.C.

Pilot Duty............. 277VAC, (1.7A), 480VA N.O.
Ballast.................. 277VAC, 1.7A
Tungsten............... 120VAC, TV3 N.O. TV2 N.C.
Gold Flash............. Yes

Year

Warranty

5

V100

V200D

VICTORY 100 & 200 SERIES

Year

Warranty

5

HQ0001833.B 01131