ENVIRONMENTAL SENSORS

Z204900-0K

PAGE 1

©2011 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

06114

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

TM

INSTALLATION GUIDE

Duct Mounted Environmental CO

2

Sensors

Installer’s Specifications

Input Voltage

20 to 30VDC, 24AC

Analog Output

CDE models: 4-20mA (clipped & capped)/0-10VDC (selectable)

CDL

models: 4-20mA (clipped & capped)/0-5VDC/0-10VDC (selectable)

Sensor Current Draw

100mA Maximum

Operating Temperature Range

0° to 50°C (32° to 122°F)

Operating Humidity Range

0-95% (noncondensing)

Housing Material

High impact ABS plastic

CO2 Transmitter:

Sensor Type

Non-dispersive infrared (NDIR), diffusion sampling

Output Range

0-2000 ppm or 0-5000 ppm, user selectable on CDL models,

0-2000 ppm on CDE models

Accuracy

±30 ppm ±2% of measured value*

Repeatability

±20 ppm ±1% of measured value

Response Time

<60 seconds for 90% step change

RH Transmitter**:

HS Sensor Digitally profiled thin-film capacitive (32-bit mathematics); U.S. Patent 5,844,138

Accuracy

±2% from 10 to 80% RH @ 25°C; Multi-point calibration NIST

Hysteresis

1.5% typical

Linearity

Included in Accuracy spec.

Stability

±1% @ 20°C (68°F) annually, for two years

Output Range

0 to 100% RH

Temperature Coefficient

±0.1% RH/°C above or below 25°C (typical)

Temperature (Transmitter)**:

Sensor Type

Solid-state, integrated circuit

Accuracy

±0.5°C (±1°F) typical

Resolution

0.1°C (0.2°F)

Output Range

10° to 35°C (50° to 95°F)

Relay Contacts**:

1 Form C

1A@30VDC, resistive; 30W max.

Specified accuracy with 24VDC supplied power with rising humidity. RTD/Thermistors in wall

packages are not compensated for internal heating of product.

EMC Conformance: EN 61000-6-3:2001 (Amended by A11:2004) Class B, EN 61000-6-1:2001

EMC Test Methods: CISPR 22:2006, IEC 61000-4-2:2001, IEC 61000-4-3:2006, IEC 61000-4-4:2004,

IEC 61000-4-6:2006, IEC 61000-4-8:2001, IEC 61000-4-11:2004

EMC Special Note: Connect this product to a DC distribution network or an AC/DC power adaptor

with proper Surge protection (EN 61000-6-1:2001 specification requirements).

* Measured at NTP

** Not available on CDE

Note: Rough handling and transportation may cause a temporary reduction of CO

2

sensor

accuracy. With time, the ABC function will tune the readings back to the correct accuracy range.

The default tuning speed is limited to 30 ppm per week.

CD SerieS

CD SerieS

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.
• Read and understand the instructions before installing
this product.
• Turn off all power supplying equipment before working on it.

• The installer is responsible for conformance to all applicable codes.

CDE

CDL

QUICK INSTALL

1. Using the mounting diagram on page 2, or using the housing as a template, mark

and drill the four mounting holes on the duct. The centerline through the housing
must be parallel to the air flow through the duct.

2. Rotate the duct probe so that its widest surface is perpendicular to the air flow in

the duct.

3. Insert the probe and secure the sensor to the duct with the sheet metal screws

provided, making sure that the provided gasket material is compressed between
the sensor housing and the air duct.

4. Wiring. See wiring diagrams on next page.

PRODUCT IDENTIFICATION

RH Option

H = RH2%
X = NO RH

CDL

DELUXE MODEL:

S

Temp

T = Temp
X = No Temp
(Stop Here)

Sensor Type

A = Transmitter
B = 100R Platinum, RTD
C = 1k Platinum, RTD
D = 10k T2, RTD, Thermistor
E = 2.2k, Thermistor
F = 3k, Thermistor
G = 10k CPC, Thermistor
H = 10k T3, Thermistor
J = 10k Dale, Thermistor
K = 10k w/11k shunt, Thermistor
M = 20k NTC, Thermistor
N = 1800 ohm, Thermistor
R = 10k US, Thermistor
S = 10k 3A221, Thermistor
T = 100k, Thermistor
U = 20k “D”, Thermistor

Optional Cal Cert.

Blank = None
1 = 1 pt Temp Cert
2 = 2 pt Temp Cert

CDE

(no options)

ECONOMY MODEL:

DIMENSIONS

6.7"

(170 mm)

3.1"

(78 mm)

7.8"

(97 mm)

2.4"

(61 mm)

10.2"

(258 mm)