Veris Industries NSC Datasheet User Manual

Cables, Sc, sc-c, sc-h, & nsc, Le ak dete ction

Advertising
background image

LE

AK DETE

CTION

VERIS INDUSTRIES

800.354.8556

+1 503.598.4564

www.veris.com

Cables

Highly Flexible, Resists Bends

and Kinks, Abrasion Resistant

FEATURES

Strong, durable, and abrasion resistant

Expansion with mating end connectors...easy installation

Available in pre-measured and custom lengths with pre-installed end
connectors...installation flexibility

Plenum rated and UL listed

Highly accurate alarm notification...no false alarms

SC, SC-C, and SC-H cables detect the presence of specific fluids...application
versatility

DESCRIPTION

Sensing and non-sensing cables are designed for use with Zone and Distance Read

panels. The sensing cables detect the presence of liquid, and send a signal to the

panel. The panel generates an alarm and pinpoints the exact location of the leak or

spill along the cable’s length. Sensing cables are designed for the highest accuracy

and maximum reliability.

SC water detection cable senses the presence of water or other conductive fluid. SC-C

chemical sensing cable detects the presence of chemicals (see Specifications for list).

SC-H hydrocarbon sensing cable locates hydrocarbons within 1 foot (0.33 m) of the

actual leak, with as little as 2 inches (51 mm) of wetted cable, and is impervious to

the presence of water.

NSC non-sensing cable is used to extend the control panel’s leader cable to an area

where SC detection cable is needed. It also bridges lengths of SC detection cable in

areas where sensing is not required. Invisible to the control panel, the non-sensing

cable does not affect the accuracy of readings or limit the amount of water detection

cable that can be connected to a control panel. NSC cables are only compatible with

systems using SC water detection cables.

All cables are highly flexible, durable, and kink-resistant. They lie flat after

installation, and they are abrasion resistant. The cables are plenum rated and UL

listed making them ideal for use under raised floors and areas where plenum rated

cable is required. Choose a pre-specified cable length or a custom length for your

convenience and installation flexibility.

SPECIFICATIONS

Plenum Rating

SC: CL2P/CMP C(UL); NSC: CL3P/CMP C(UL) California State Fire Marshall approved

Shear Strength

SC/NSC: >180 lbs (>81.65 kg); SC-C: 160 lb (72.6 kg)

Cut Through Resistance

SC/NSC: >40 lbs (>18.2 kg) with 0.005” (0.13 mm) blade; SC-C: >50 lbs (>27.7 kg) with 0.005” (0.13 mm) blade

Abrasion Resistance

SC/NSC: 60 cycles per UL 719; SC-C: >65 cycles per UL719

Connector

SC/NSC: 4 pin, 1” (25.4 mm) diameter, circular, locking, 4 pin; SC-C: 0.5” (13 mm) diameter

Operating Environment:

Temperature

SC/NSC: 0° to 75°C (32° to 167°F); SC-C: 90°C (194°F) max.; SC-H: -20° to 90°C (-4° to 140°F)

Humidity

SC/NSC: 5% to 95% RH non-condensing

Altitude

SC/NSC: 10,000 ft. (3,048 m) max.

Storage Environment

SC: -30° to 85°C (-22° to 185°F); NSC: 0° to 75°C (32° to 167°F)

Standard Lengths:

SC-10/NSC-10

10 ft. (3.1 m)

SC-25/NSC-25

25 ft. (7.7 m)

SC-50/NSC-50

50 ft. (15.3 m)

SC-100/NSC-100

100 ft. (30.5 m)

Weight

0.02 lbs/ft (29.7 g/m)

Chemical Resistance, SC-C*

In accordance with ASTM D543, cable functions normally after seven days’ exposure to the following:

Fresh deionized water, tap water, sulfuric acid (98%), sulfuric acid (50%), hydrochloric acid (37%),

sodium hydroxide (10%), aqua regia, ethylene glycol (60% in DI water)

Chemical Resistance, SC-H*

In accordance with ASTM D543, cable functions normally after seven days’ exposure to the following:

Unleaded gasoline, #1 diesel fuel, #2 diesel fuel, JP5 jet fuel, JP8 jet fuel, Jet-A jet fuel, xylene, kerosene, cigarette lighter fuel (completely water resistant)

Agency Approvals

SC: CE; UL E162948; RoHS compliant

NSC: UL E118871; UL 13, power limited circuit cable; UL 444, communication cables; NFPA 262; plenum flame test (UL 910); NEC Articles 725 and 800; RoHS compliant

* Prolonged exposure to concentrated ketones may cause temporary reduction of sensitivity; call for details.

SC

NSC

SC, SC-C, SC-H, & NSC

SC-C

SC-H

HQ0001799.B 01131