SPECIFICATIONS

Inputs:

Voltage Input

208 to 480VAC, 50/60 Hz RMS 1 ² 3

Current Input

Up to 2400A continuous per phase ² 3

Accuracy:

System Accuracy

±1% of reading from 10% to 100% of the rated current of the CTs, accomplished by matching the CTs with electronics and calibrating them as a system

Outputs:

Type

Modbus RTU 4 5

Baud Rate

9600, 8N1 format

Connection

RS-485, 2-wire + shield

Environmental:

Operating Temperature Range

0° to 60°C (32° F to 140°F), 50°C (122°F) for 2400A

Humidity Range

0 - 95% noncondensing

Agency Approvals UL508

Approved for California CSI Solar applications (check the CSI website for model numbers).

¹ Do not install on the line or load side of a VFD unit, or on any other equipment generating harmonics. For line side applications, use the E5x Series meters.

² Contact factory to interface for voltages above 480VAC or current above 2400 Amps.

3 Do not apply 600 V Class current transformers to circuits having a phase-to-phase voltage greater than 600 V, unless adequate additional insulation is applied between the primary conductor and the current transformers.

Veris assumes no responsibility for damage of equipment or personal injury caused by products operated on circuits above their published ratings.

4 Detailed protocol specifications are available at: http://www.veris.com/modbus

5 Other protocols available. Please consult factory.

Enercept® Networked Power

Transducers (Modbus® RTU)

Year

Warranty

5

FEATURES

Revenue Grade measurements

Precision electronics and current transformers in a single package...reduces the

number of installed components...creating significant labor savings

Monitor energy parameters (kW, kWh, kVAR, PF, Amps, Volts) at up to 63

locations on a single RS-485 network...greatly reduces wiring time and cost

Fast split-core installation eliminates the need to remove conductors...saves

time and labor

Smart electronics eliminate CT orientation concerns...fast trouble-free

installation

CSI approved...eases submission process for California Solar Initiative

DESCRIPTION

The Enercept H8035 and H8036 Series are innovative three-phase networked
(Modbus RTU) power transducers that combine measurement electronics and high
accuracy industrial grade CTs in a single package. The need for external electrical
enclosures is eliminated, greatly reducing installation time and cost.

There are two application-specific platforms to choose from. The Basic Enercept
energy transducers (H8035) are ideal for applications where only kW and kWh
are required. The Enercept Enhanced power transducers (H8036) output 26
variables including kW, kWh, volts, amps, and power factor, making them ideal for
monitoring and diagnostics.

Color-coordination between voltage leads and CTs makes phase matching easy.
Additionally, the Enercept automatically detects and compensates for phase
reversal, eliminating the concern of CT load orientation. Up to 63 Enercepts can be
daisy-chained on a single RS-485 network.

APPLICATIONS

Energy managment and performance contracting

Monitoring for commercial tenants

Activity-based costing in commercial and industrial facilities

Real-time power monitoring

Load shedding

Integral Monitoring Solution

Eliminates the Need for

Separate Enclosures

U.S. Patent No. 6,373,238

H8035/H8036

H8035 & H8036 SERIES

BACnet

connec

tivity

via new

E8950

Gateway

HQ0001711.C 01131