Veris Industries HW PROTOCOL SERIES Install User Manual

Hw protocol, Notice, Installation guide

Advertising
background image

Z205863-0C

PAGE 1

©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

01122

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

TM

ENVIRONMENTAL SENSORS

INSTALLATION GUIDE

Wall Mounted Humidity Sensors

with Protocol Communication

Installer’s Specifications

Input Voltage

12 to 30VDC, 24VAC; 100mA max.

Operating Temperature Range

0° to 50°C (32° to 122°F)

Housing Material

High impact ABS plastic , UL 94 VO

Protocol

BACnet or Modbus (selectable)

Connection

2-wire RS-485

Data Rate

9600, 19200, 38400, 57600 (Modbus), bps (selectable)

9600,

19200, 38400, 76800 (BACnet), bps (selectable)

Parity

None/Odd/Even (selectable-Modbus)

None

(BACnet)

Address Range 1-127

RH Transmitter:

HS Sensor

Replaceable digitally profiled thin-film capacitive

(32-bit

mathematics); U.S. Patent 5,844,138

Accuracy*

±1% from 12 to 60% RH; ±2% from 10 to 80% RH;

NIST

traceable multi-point calibration

Reset Rate**

24 hours

Stability

±1% @ 20°C (68°F) annually for two years

Hysteresis

1.5% typical

Operating Humidity Range

0 to 100% RH, noncondensing

Operating Temperature Range

10° to 35°C (50° to 95°F)

Temperature Coefficient

±0.1% RH/°C above or below 25°C (typical)

Temperature Transmitter Option:

Sensor Type

Solid-state, integrated circuit

Accuracy

±0.5°C (±1°F) typical

Resolution

0.1°C (0.2°F)

Range

10° to 35°C (50° to 95°F)

Setpoint Slider Resolution Option

1% full scale

Override Button Option

Remotely readable and resettable

* Specified accuracy with 24VDC supplied power with rising humidity.

** Reset rate is the time required to recover to 50% RH after exposure to 90% RH for 24 hours.

Note: RTD/Thermistors in wall packages are not compensated for internal heating of product.

HW Protocol

HW Protocol

DIMENSIONS

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.
• Read and understand the instructions before installing
this product.
• Turn off all power supplying equipment before working on it.

• The installer is responsible for conformance to all applicable codes.

PRODUCT IDENTIFICATION

QUICK INSTALL

1. Select a mounting location away from ventilation sources. The sensor should be

mounted on a vertical wall, about 4 1/2 feet above the floor.

2. Affix the backplate to the wall.

3. Wire the device. Refer to wiring diagram.

4. Install Cover.

HW

Local Display

L = LCD
X = No Display

Protocol

= Protocol

P

RH Option

1 = RH 1% NIST
2 = RH 2% NIST
H = RH 2%

Temp. Option

X = No temp. option
T = Temp. Transmitter

Temp. Cal. Cert.

X = No
1 = 1 pt. cal. cert.*
2 = 2 pt. cal. cert.*
3 = 3 pt. cal. cert.*

Option

Blank = None
1 = Pushbutton override
2 = Setpoint slider
3 = Pushbutton override +
set point slider

Housing

Blank = Cloud white
B = Black

4.8"

(122 mm)

1.2"

(30 mm)

3.5"

(89 mm)

T

Observe handling precautions for static sensitive

devices to avoid damage to the circuitry which

would not be covered under the factory warranty.

* Only available if temperature option is selected.