NETWORK INTEGRATION

INSTALLATION GUIDE

Specifications

AC Power Source

Dedicated 120/240 VAC, line-to-neutral; fused

Fuse Ratings

200mA at 250V 5x20 mm fast blow

AC Power Voltage Tolerance

90-132VAC for 120V

AC Power Frequency

50/60 Hz

AC Power Termination

2-position Euro style pluggable connector

(max. wire size 12 gauge)

Terminal Block Torque

4.9 in-lb (0.56 N-m)

Alternate DC Power Source

12VDC, 300mA unfused

Environmental:

Operating Temperature Range

0° to 50°C (32° to 122°F)

Operating Humidity Range

<95% RH, non-condensing

Storage Temperature Range

-20° to 70°C (68° to 158°F)

Network Communications:

Interface

Downstream: RS-485; Upstream: RS-485, RS-232

Protocol

Modbus RTU

Baud Rate

UI-selectable 2400, 4800, 9600, 19200

Parity

UI-selectable NONE, ODD, EVEN

Communication Format

8-data-bits, 1-start-bit, 1-stop-bit

RS-485

¼ load transceivers; duplex is UI-selectable 2-wire or 4-wire;

5-position Euro-style pluggable connector

RS-232 (Upstream only)

DCE, no handshaking; DB-9 connection;

pin

2: transmitted data from display;

pin

3: received data to display; pin 5: ground

Terminal Block Torque

4.4 in-lb (0.5 N-m)

UI Switch Inputs:

Number/Function

4 (Meter, Up, Down, Select)

Auxiliary Input (Remote Alarm):

Type

Contact closure or pull-to-ground

Isolation

Optical to 2500VAC

Sense

UI-selectable N.O. or N.C.

Terminal Block Torque

3.5 to 4.4 in-lb (0.4 to 0.5 N-m)

LCD:

Size

1” x 4” visible area, 2 lines x 16 characters per line

Backlight

Green, UI-adjustable brightness in 10 steps

Status (Tri-Color LED)

Green = normal operation; Yellow = warning; Red = alarm

Network Display

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

• Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.

Failure to follow these instructions will result in death or serious injury.

A qualified person is one who has skills and knowledge related to the construction and

operation of this electrical equipment and the installation, and has received safety

training to recognize and avoid the hazards involved.

NEC2009 Article 100

No responsibility is assumed by Veris Industries for any consequences arising out of the

use of this material.

DANGER

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.

• The installer is responsible for conformance to all applicable codes.

• Mount this product inside a suitable fire and electrical enclosure.

FCC PART 15 INFORMATION
NOTE: This equipment has been tested by the manufacturer and found

to comply with the limits for a class A digital device, pursuant to part
15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference when the equipment is
operated in a commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if not installed and
used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in
a residential area is likely to cause harmful interference in which case
the user will be required to correct the interference at his own expense.
Modifications to this product without the express authorization of
Veris Industries nullify this statement.

PRODUCT IDENTIFICATION

MODEL

DESCRIPTION

H8932

without enclosure

H8936

with enclosure

H8932/H8936

SUPPORTED METERS

MODEL

DESCRIPTION

H8035/H8036

Enercept Power Meter

H8163 with H8163-CB

Energy Meter

H663/H704

Branch Circuit Meter

H8238

Multi-Circuit Monitor

E5xCx

Power and Energy Meter, Modbus Protocol versions

E30/E31

Panelboard Monitoring System

WARNING

LOSS OF CONTROL
∙ Assure that the system will reach a safe state during and after a control path failure.
∙ Separate or redundant control paths must be provided for critical control functions.
∙ Test the effect of transmission delays or failures of communication links.

1

∙ Each implementation of equipment using communication links must be individually

and thoroughly tested for proper operation before placing it in service.

Failure to follow these instructions may cause injury, death or equipment damage.

1

For additional information about anticipated transmission delays or failures of the link, refer to

NEMA ICS 1.1 (latest edition). Safety Guidelins for the Application, Installation, and Maintenance

of Solid-State Control or its equivalent in your specific country, language, and/or location.

Control system design must consider the potential failure modes of control paths and, for

certain critical control functions, provide a means to acheive a safe state during and after a

path failure. Examples of critical control functions are emergency stop and over-travel stop.

Advertising