CP Name

Type

NV Num.

R/W

Applies To

Range

Default Value

Description

cpPhaseLossImbal

UCPTphLossImbal
(UCP_Type_10 w/o

resource files)

(SNVT_count ref.)

19

R/W

“Meter” Function

Block

1 - 99 (%)

25(%)

Phase Loss Imbalance Threshold in percent. For

a 3-phase Y(3+N) system (type 40), both Line

to Neutral and Line to Line voltages are tested.

In a 3-phase delta system (type 31), only the

Line to Line voltages are examined. In a single

split-phase (2+N) system (type 12), just the

Line to Neutral voltages are compared.

cpDemSubintLen

UCPTDemSubintLen
(UCP_Type_11

w/o resource files)

(SNVT_count ref.)

20

R/W

“Meter” Function

Block

0, 10 - 32767

(seconds)

900 (seconds)

Sub-Interval Length in seconds. For sync-to-

comms, set this to 0 and use nviDemSubintRes

to externally restart the sub-interval.

cpDemSubintCnt

UCPTDemSubintCnt
(UCP_Type_1 w/o

resource files)

(SNVT_count ref.)

21

R/W

“Meter” Function

Block

1 - 6

1

Number of Sub-Intervals per Demand Interval.

Sets the number of sub-intervals that make

a single demand interval. For block demand,

set this to 1.

PROPAGATION CONTROL
cpMaxNvSntPerSec UCPTnvUpdtLimit

(UCP_Type_2 w/o

resource files)

(SNVT_count)

29

R/W

“Meter” Function

Block

0 - 65535

10

Limits the total number of updates sent out per

second for network variables in the following

categories: Energy, Power, Voltage, Current,

Power Factor, Frequency, Pulse Counters,

Startup Count, and Alerts. If more than the

number of updates specified is queued to be

sent out in any 1 second period, the excess

updates are delayed until the next second

to reduce network traffic. This configuration

property is provided to give rough burst

control. The number of packets sent per

second will vary based on the connection

types (ACK, UNACK, etc.) and updates from

other network variables that are not controlled

by this configuration property.

cpAllEnergy

SCPTminSndT

1

R/W

All energy output

network variables

0 - 1 hour,

49 minutes,

13 seconds,

500ms (6553.5

seconds)

15 seconds

Throttle for all energy output network variables.

After propagation of a network variable,

updates to the same network variable are

blocked for the time set by this configuration

property. The configuration property is shared,

but each energy output network variable has

its own independent throttle counter that

resets to the value specified by this CP after it

has been propagated.

cpAllPower

SCPTminSndT

2

R/W

All power output

network variables

0 - 1 hour,

49 minutes,

13 seconds,

500ms (6553.5

seconds)

15 seconds

Throttle for all power output network variables.

After propagation of a network variable,

updates to the same network variable are

blocked for the time set by this configuration

property. The configuration property is shared,

but each power output network variable has

its own independent throttle counter that

resets to the value specified by this CP after it

has been propagated.

cpAllVoltage

SCPTminSndT

3

R/W

All voltage output

network variables

0 - 1 hour,

49 minutes,

13 seconds,

500ms (6553.5

seconds)

15 seconds

Throttle for all voltage output network

variables. After propagation of a network

variable, updates to the same network

variable are blocked for the time set by this

configuration property. The configuration

property is shared, but each voltage output

network variable has its own independent

throttle counter that resets to the value

specified by this CP after it has been

propagated.

Advertising