PAGE 1

©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

03121

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

TM

OCCUPANCY SENSORS

INSTALLATION GUIDE

Auxiliary Relay

Installer’s Specifications

Storage Temperature

-29° to 65°C (-20° to 150°F )

Operating Temperature

0° to 40°C (32° to 104°F)

Maximum Humidity

90% RH non-condensing

Control Input

24 VDC, 36 mA nominal

Relay Contacts:

Horsepower Rating

1 HP@120 V

Switching Capacity

120 VAC, 60 Hz; 15 A tungsten 1800 W

120/277 VAC, 60 Hz; 20 A ballast

AA48

AA48

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

• Follow safe electrical work practices.

See NFPA 70E in the USA, or applicable local codes.

• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION

Failure to follow these instructions will result in death or serious injury.

DANGER

OPERATION

The AA48 Auxiliary Relay is a low-voltage relay device that expands the switching
capacity of an AA47 power pack, controlling additional circuits in response to a signal
from an MSC occupancy sensor. The relay has an SPST, normally open output that is
controlled directly by the MSC. The relay is rated for maximum 15 A tungsten and 20
A ballast loads.

Mount the AA48 either inside or outside a standard junction box using a 1/2-in.,
threaded EMT nipple. Route power to the sensor using plenum-rated cable.

INSTALLATION

1. Provide separate overcurrent protection in accordance with the National Electrical

Code® and applicable local codes.

2. Use copper wire only.

3. Confirm that the device rating is appropriate for your application.

4. Mount the auxiliary relay to a suitable junction box using the 1/2-in., threaded

nipple and lock. The auxiliary relay is plenum-rated, and can be mounted to the

inside or the outside of a junction box or fixture in a ceiling plenum.

5. Connect the auxiliary relay as shown. Use approved wire nuts for electrical

connections.

Load

AA47

Power

Pack

AA48 Optional

Auxiliary

Relay

Red

Red

Red

Hot

Neutral

Hot

White

Black

+24VDC (Red)

0VDC (Blk)
Control (Blue)

Override

OFF

Ext. Override

OFF

Load

Load

Sensor

Relay

Common Black

Control Input Blue

Red Switched Hot

Red Hot

120/277 VAC, 60 Hz

From Sensor Output

Line Voltage

INSIDE

From Sensor Output

Line Voltage

OUTSIDE

MOUNTING OPTIONS

SCHEMATIC DIAGRAM

SYSTEM DIAGRAM