Load Status Switch

Installer’s Specifications

Sensor Power

Line powered

Operating Temperature

-15° to 60°C (5° to 140°F)

Operating Humidity

10-90% RH, non-condensing

LED Status

GREEN LED=status normal; RED LED=status alarm

Frequency

50/60 Hz

Wire Specifications:

Lead Length

14”(356mm) min.

Gauge

UL1015; Neutral: 18AWG; Line: 12AWG; Status: 16AWG

Agency Approvals

UL 508, E150462

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

• Follow safe electrical work practices.

See NFPA 70E in the USA, or applicable local codes.

• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION

Failure to follow these instructions will result in death or serious injury.

DANGER

H280, H280NC

TM

280, 280NC

DIMENSIONS

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.

• The installer is responsible for conformance to all applicable codes.

• Mount this product inside a suitable fire and electrical enclosure.

INSTALLATION

Disconnect and lock out all power sources before beginning the

installation.

1. Using the threaded nipple, connect the switch to the desired enclosure through a

knock out hole.

2. Secure with the conduit nut provided.

3. Connect load in series:

• Choose one orange wire and connect to load side of switch.
• Choose the other orange wire and connect to load.

4. Connect status output:

• Connect the grey wires (or brown wires for H280NC) to controller digital

input. Not polarity sensitive.

5. Secure the enclosure and reconnect power.

Wires that are not terminated must be isolated or insulated, i.e. wire nut.