Veris Industries LD1000 Install User Manual

Ld1000, L d 1 0 0 0, User guide

Advertising
background image

L D 1 0 0 0

USER GUIDE

LD1000

1. LD1000

Installation

The LD1000 is a wall mounted device, and mounting hardware is supplied with every unit. Select a location for the

LD1000 and place the two screw anchors in the wall 4.25 inches (107.9mm) apart. Screw both screws into the wall

anchors so that approximately 1/8 inch (3.18mm) of each screw is showing. (It may be necessary to adjust the

screws – in or out – so that the unit fits snugly to the wall.) Remove the front cover from the LD1000 and hang the

rear of the unit on the screws. Pull the unit toward the ground, so the screws nestle in the top of each keyhole and

securely fasten the unit to the wall. Before reattaching the front of the unit, make all wiring connections and set all

switches to the desired setting (see below for configurations).

2. Power

Connections

The LD1000 requires 24VAC or 24VDC. Make sure to wire the appropriate power to the appropriate terminal blocks

on the LD1000 to avoid damage or injury (ie DC power must only be wired to the terminal blocks labeled “DC IN”

and AC power must only be wired to the terminal blocks labeled “AC IN”). If using DC power, the power supply

must be an isolated power supply (part #WA-DC-24-ST).

3. Cable

Installation

The LD1000 requires a separate leader cable (part #LC-KIT) that connects the sense cable to the unit and

terminates the line of sensing cable properly. Connect the stripped end of the 15 foot (4.57m) leader cable to the

terminal block labeled TB1 on the main board of the LD1000. From left to right, with the screws of the terminal

block connector facing up, the leader cable wires should be connected white, black, green, and red. Once the

leader cable is plugged into the terminal blocks, it is ready to be connected to the leak detection cable. To do this,

unscrew the end terminator from the end of the leader cable. Attach the first length of water leak detection cable to

the leader cable. Route the water leak detection cable according to a cable layout diagram, if provided. Secure the

end terminator on the unoccupied end of the leak detection cable.

4. Leak

Sensitivity

Adjust R25 (see diagram below) to set the desired leak sensitivity. By default, it is set to the mid-sensitivity setting

(150uA) and may be adjusted to the low (300uA) or high (25uA) sensitivity setting by turning the dial.

Dipswitch Settings

SW1-1: Configures the output relays as supervised or non-supervised. If the relays are supervised, the relays will

remain on until either power is disabled or an alarm is detected (relay will turn off). If the relays are non-supervised,

the relays will turn on upon an alarm being detected.

Off – Non-supervised (Factory Default)

On – Supervised