Veris Industries H6812 SERIES Install User Manual

Notice, Danger, Installation guide

Advertising
background image

Z202815-0F

PAGE 1

©2011 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

02111

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

TM

POWER MONITORING

INSTALLATION GUIDE

Installer’s Specifications

Output at Rated Current

0.333 or 1 VAC

Accuracy

1% from 10% to 100% of rated current

Frequency Range

50/60 Hz

Leads

18AWG, 600VAC, UL 1015 twisted pair, 6 ft. (1.8m) standard length

Weight

H6810: 0.340 kg; H6811: 0.580 kg; H6812: 0.870 kg

Operating Temperature Range

-15° to 60°C (5° to 140°F)

Storage Temperature Range

-40° to 70°C (-40° to 158°F)

Humidity Range

0-95% noncondensing

Max. Voltage L-N Sensed Conductor

600VAC (basic insulation rating) *

Altitude of Operation

3km max.

Installation Category

Cat II or Cat III

* Do not apply 600V Class current transducers to circuits having a phase-to-phase voltage greater

than 600V, unless adequate additional insulation is applied between the primary conductor and

the current transducers. Veris assumes no responsibility for damage of equipment or personal
injury caused by products operated on circuits above their published ratings.

1 VAC and 0.333 VAC Current Transducers

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

• Follow safe electrical work practices.

See NFPA 70E in the USA, or applicable local codes.

• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION

Failure to follow these instructions will result in death or serious injury.

DANGER

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.

• The installer is responsible for conformance to all applicable codes.

• Mount this product inside a suitable fire and electrical enclosure.

• This product provides basic insulation only.

PRODUCT IDENTIFICATION

QUICK INSTALL

Installation must be performed by a qualified electrician.

Disconnect and lock out power to the primary circuit

before installing these current transducers (CTs).

1. Connect the transducer output leads to the meter inputs. The white wire is the X1

lead.

2. Depress the tabs on one end of the current transducer to open it and slip it over the

primary leads. Note labeling on product indicating “source side.”

3. Check the core ends on both sections of the CT to assure there is no rust or debris in

the closure areas.

4. Close and latch the CT, and mount it securely.

5. Reconnect power to the panel.

Optional mounting kit available. See Veris AH06.

H6810, H6811, H6812

H681

Model/Amps

Small:

0-100 = 100A
0-200 = 200A
0-300 = 300A

Medium:

1-400 = 400A
1-600 = 600A
1-800 = 800A

-

Output Type

1V = 0-1VAC
0.3V = 0-0.333VAC

Large:

2-800 = 800A
2-1200 = 1200A
2-1600 = 1600A
2-2000 = 2000A
2-2400 = 2400A

Documentation must be consulted where this symbol is used on the product.

This symbol indicates an electrical shock hazard exist.

Always use this product in the manner specified or the protection provided by the
product may be impaired. This product must be installed in an appropriate Fire and
Electrical enclosure per local regulations.