ENVIRONMENTAL SENSORS

INSTALLATION GUIDE

Environmental CO

2

Remote Mount Sensor

Installer’s Specifications

Input Voltage

20 to 30VDC, 24AC

Analog Output

4-20mA (clipped and capped)/0-5VDC/0-10VDC (selectable)

Sensor Current Draw

100mA max.

Operating Temperature Range

0° to 50°C (32° to 122°F)

Operating Humidity Range

0-95% (noncondensing)

Housing Material

High impact ABS plastic

CO2 Transmitter:

Sensor Type

Non-dispersive infrared (NDIR), diffusion sampling

Output Range

0-2000 ppm or 0-5000 ppm, user selectable

Accuracy

±30 ppm ±5% of measured value

Repeatability

±20 ppm ±1% of measured value

Response Time

<60 seconds for 90% step change

when

used with supplied 3 ft. sampling tube (AA50)

Relay Contacts:

1 Form C

1A@30VDC, resistive; 30W max.

EMC Conformance: EN 61000-6-4:2001 Class B, EN 61000-6-1:2001

EMC Test Methods: CISPR 11:2004, IEC 61000-4-2:2001, IEC 61000-4-3:2002, IEC

61000-4-4:2004, IEC 61000-4-5:2001, IEC 61000-4-6:2004, IEC 61000-4-8:2001, IEC

61000-4-11:2004

EMC Special Note: Connect this product to a DC distribution network or an AC/DC power

adaptor with proper surge protection (EN 61000-6-1:2001 specification requirements).

When directly measuring outside air, ensure that the air temperature reaching the sensor

is between 0° and 50°C.

Note: Rough handling and transportation may cause a temporary reduction of CO

2

sensor

accuracy. With time, the ABC function will tune the readings back to the correct accuracy range.

The default tuning speed is limited to 30 ppm per week.

CRLSxx

CRLSxx

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.
• Read and understand the instructions before installing
this product.
• Turn off all power supplying equipment before working on it.

• The installer is responsible for conformance to all applicable codes.

PRODUCT IDENTIFICATION

QUICK INSTALL

1. Mark and drill at least two mounting holes for the sensor.

2. Secure the sensor the the mounting surface.

3. Attach the provided pickup tubes, ensuring the supply line is connected to the

front (high) port and the return line is connected to the back (low) port.

4. Wire the device. See the Wiring section for more information.

5. Power the device.

6. Follow Configuration procedure (page 3).

CRL

AA50

MODEL

DESCRIPTION

CRLSxx

CO2 Based Remote Mount Sensor

DIMENSIONS

0.4" x 0.2"

(11mm x 5mm)

6.7"

(175 mm)

0.3"

(6 mm)

typ

1"

(26 mm)

typ

5.7"

(144 mm)

3.1"

(78 mm)

6.7"

(170 mm)

3.1"

(78 mm)

2.4"

(61 mm)

MOUNTING DIAGRAM

Advertising