Veris Industries HT SERIES Install User Manual

Ht series, Notice, Installation guide

Advertising
background image

VERIS INDUSTRIES

environmental SenSorS

inStallation GUiDe

Z203269-0P

PAGE 1

©2010 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

06101

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

LCD Wall Mount with Analog Setpoints

1% NIST, 2% NIST, 2%, 3%, 5%

Installer’s Specifications

Input Power*

15 to 30VDC/24VAC, 100mA max.

Outputs

Switch-selectable 4-20mA or 0-10V/0-5VDC

(switch affects both outputs)

RH Sensor

Digitally profiled thin-film capacitive (32-bit mathematics)

U.S. Patent 5,844,138

Accuracy at 25°C from 10-80% RH**

±2%, 3%, or 5% models

±1% at 20-50% RH (Multi-point calibration NIST traceable)

Reset Rate***

24 hours

Stability

±1% @ 20°C (68°F) annually, for two years

Linearity

Included in Accuracy spec.

Operating Humidity Range

0-100% RH (non-condensing)

Temperature Coefficient

± 0.1%RH/°C above or below 25°C (typical)

Operating Temperature Range

10°-35°C (50°-95°F)

Temperature Accuracy

± 1.0°C ( ± 1.8°F)

Scaling

RH: 0-100% RH; Temp: 10°-35°C (50°-95°F) or

0°-50°C (32°-122°F) menu selectable

Calibration Offset

RH: Adjustable ±9.9% in 0.1% increments;

Temp: Adjustable ±5.0°C (±9.9°F) in 0.1° increments

Setpoint Range

RH: 10-80% RH in 1% increments;

Temp: Minimum to Full Scale in 1° increments

* One side of transformer secondary is connected to signal common, so an isolation transformer or

dedicated power supply may be required.

** Specified accuracy with 24VDC supplied power with rising humidity

***Reset Rate is time required to recover to 50% RH after exposure to 90% RH for 24 hours

RTD/Thermistors in wall packages are not compensated for internal heating of product.

HT SerieS

HT SerieS

Dimensions

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.
• Read and understand the instructions before installing
this product.
• Turn off all power supplying equipment before working on it.

• The installer is responsible for conformance to all applicable codes.

ProDuct iDentification

quick install

1. Select a mounting location away from ventilation sources. The sensor should be

mounted on a vertical wall, about 4 1/2 feet above the floor.

2. Affix the backplate to the wall.
3. Wire the device. Refer to wiring diagram.
4. Install Cover.

Setpoint

Accuracy NIST

= Analog

1 = 1%
2 = 2%
3 = 3%
5 = 5%

HT

Temp Cal
Certificate

0 = None
1 = 1 point Cal
Validation
2 = 2 point Cal
Validation

Option

B = 100R Platinum, RTD
C = 1k Platinum, RTD
D = 10k T2, Thermistor
E = 2.2k, Thermistor
F = 3k, Thermistor
G = 10k CPC Thermistor
H = 10k T3, Thermistor
J = 10k Dale, Thermistor
K = 10k w/11k with Shunt,
Thermistor
M = 20k NTC, Thermistor
N = 1800 ohm TAC, Thermistor
Q = 1uA/C, Linitemp
R = 10k US, Thermistor
S = 10k 3A 221
T = 100k, Thermistor
U = 20k “D”, Thermistor

N = NIST
(1 & 2% only)
X = No
(2, 3, 5% only)

S

= CE

1.2"

(29 mm)

3.5"

(89 mm)

4.75"

(121 mm)

-

+

Enter

A