Take off the jumper, With dt-cam wiring mode electric lock connection, Bus pl s2+ s1+ s1 – V-Tech DT595A Manual User Manual

Page 7: Dip switch setting

Advertising
background image

With DT-CAM wiring mode

Electric Lock Connection

Door Lock Controlled with Internal Power

Door Lock Controlled with Dry Contact

Note:

1. Electronic lock of Power-on-to-unlock type

should be used.

2. The door lock is limited to 12V, and holding

current must be less than 250mA.

3. The door lock control is not timed from Exit

Button(EB).

4. The Unlock Mode Parameter of Monitor must

be set to 0 (by default).

EB

*

LOCK

Jumper position in

Connect one lock

2-3

Bus PL S2+ S1+ S1-

Note:

1. The external power supply must be used

according to the lock.

2. The jumper must be taken off before connecting.

3. Setup the Unlock Mode of Monitor for different

lock types.

* Power-on-to-unlock type:Unlock Mode=0 (by default)

* Power-off-to-unlock type:Unlock Mode=1

DIP Switch Setting

The DIP switch is designed to set the code for door station and monitor, there are two states for
each DIP switch, please refer to the following sketch map.

The audio door station DT595A can be extended an additional CCTV camera to be a video door
station. For more details about the camera, please refer to DT-CAM user instructions.

Door station DIP setting

Indoor monitor DIP setting

Bit state

Description

ON(1)

=

OFF(0)

=

ON

ON

Total 3 bits can be configured, bit-1 and bit-2 are used to assign ID code for door station, bit-3 is

used to match the video impedance.The switches can be modified either before or after installation.

There are 6 bits in total. The DIP switches are used to configure the user code for Monitors.

Bit-6 is an video impedance match switch, which have to be set to ON if match the impedance,

otherwise set to OFF.

Bit-1~Bit-5 are used to set user code, to DT595A door station, the user code should set to 0~15.

Please refer to the following settings:

Note: if the video impedance need to match, please set the bit-3 on.

1 2

3

ON

1 2

3

ON

1 2

3

ON

1 2

3

ON

ID = 0(00), set to the first door station

ID = 1(10), set to the second door station

ID = 2(01), set to the third door station

ID = 3(11), set to the fourth door station

LOCK

Take off the Jumper

POWER

SUPPLY

Bus PL S2+ S1+ S1-

1 2 3

AC~

PC6

ERL

DT595A

DT-CAM

DS

IM

Bus PL S2+ S1+ S1-

OUT IN

Monitor