Instrument modification

7 Instrument modification

7.1 Retrofitting the adjustment insert

Such a retrofitting can be necessary, e.g.
when a pressure transmitter with factory
settings must be adapted to changed meas-
urement conditions.

Note the following retrofit procedure:
• remove the outdated terminal insert
• mount new adjustment insert
• set up pressure transmitter acc. to chapter

"5 Setup"

Remove the outdated terminal insert

1

Separate pressure transmitter from
power supply.

2

Unscrew cover of the connection housing
or loosen the screws on the cover of the
external housing.

3

Remove cover.

4

Loosen connection cables on the terminal
insert.

5

Loosen the three screws of the terminal
insert.

6

Remove terminal insert and pull out plug
connection (to do this, bend locking nose
carefully towards housing centre).

Mount new adjustment insert

7

Plug the connection into the adjustment
insert (must snap in).

8

Place adjustment insert in the housing
and fasten with three screws.

9

Connect the connection cables to the
terminals.

10 Fasten the cover.
11 Reconnect the pressure transmitter to

power supply.

Setup of pressure transmitter

see chapter "5 Setup".