32

Pressure transmitter D85

2

2

2

1)

Ri < 250

9

4 ... 20 mA

Setup

5.5 Adjustment with PC directly on the sensor

(electronics versions I, K and L)

For connection of the PC to the sensor, the interface converter VEGACONNECT 2 is required.

Connection of the PC to the sensor

Insert VEGACONNECT into the serial interface of the PC and insert the two-wire cable of
VEGACONNECT into the CONNECT socket of the sensor.

Connection of the PC to the signal cable

Connect the two-wire cable of VEGACONNECT 2 to the signal cable leading to the sensor.

Connection configuration with pressure transmitter directly on active PLC

(electronics versions I, K and L)

• Two-wire technology, power supply from active PLC.
• Output signal 4 … 20 mA (passive).
• Adjustment with PC, HART

®

handheld or adjustment insert located or in the sensor or the

external connection housing.

1)

If the resistance of the processing system (PLC)
connected to the 4 … 20 mA signal output is less
than 200

W, a resistor of 250 W must be connected

to the connection cable during adjustment.

The digital adjustment signal would be considerably
damped or short-circuited through insufficient
resistance of a connected processing system, and
digital communication with the PC would not be
ensured.

VEGA-
CONNECT 2

PLC