Switch point adjustment (only possible on VEGAMET 308)

• Set A/B-switch acc. to the following description to the desired mode A or B.

Mode A

When exceeding the adjusted max. level:

Relay de-energized
Relay control lamp lights
Terminals 9-10 are connected through relay

Mode B

When decreasing the adjusted min. level:

Relay de-energized
Relay control lamp lights
Terminals 9-10 are connected through relay

• Adjust switch point for min. level

Push button for adjustment of the min. switch point and adjust the potentiometer of
the indicating instrument to the desired min. value.

• Adjust switch point for max. level

Push button for adjustment of the max. switch point and adjust the potentiometer
of the indicating instrument to the desired max. value.

Adjustment for single-point switching

• Push button for adjustment of the max. switch point and set the indicating instru-

ment with the respective potentiometer to "0".

• Push button for adjustment of the min. switch point and set the indicating instru-

ment with the respective potentiometer to the required value.

Note:
The switching hysteresis is in this case 0,5 %.