Pressure transmitter D90 (Profibus PA)

Mounting

2 Mounting

2.1 Mounting instructions

The pressure transmitter can be mounted in
any position. Cable entries must point down-
wards to avoid moisture ingress. For this
purpose, the housing can be rotated by 330°
in relation to the mounting part.

A seal, appropriate for the respective con-
nection, must be used for mounting. This seal
is either supplied with the pressure transmit-
ter or must be provided by the customer.

2.2 Compensation of the atmos-

pheric pressure

On instruments for gauge pressure meas-
urement, the atmospheric pressure is com-
pensated via a breather facility integrated in
the housing.

Pressure transmitter with housing

- via an integrated breather facility (PTFE

use

1)

), protection IP 66

- via the capillaries of a special cable con-

nected to the terminals, protection IP 67

Pressure transmitter with direct cable
outlet

- via the capillaries of a special cable con-

nected to the terminals, protection IP 68

We recommend leading a special cable to
the processing unit and carrying out the
pressure compensation via the integrated
breather facility there.

Processing unit

Observe the following instructions:
- there must generally be the same atmos-

pheric pressure in the breather facility and
on the vessel

- the pressure compensation must be made

in dry environment

- with perpendicular wall mounting, cable

entries must point downward to avoid
moisture ingress and buildup on the
breather facility.