VEGA VEGACOM 557 VEGA ASCII protocol User Manual

Page 26

Advertising
background image

26

VEGACOM 557 VEGA ASCII

4.1 Enquiry for VEGAMET with three or less values per instrument

Low resolution = Switch 2.2 = OFF

VEGAMET series 509 and 512 instruments have max. 3 DCS outputs. Series 513, 514 and 515
instruments can assign max. 7 DCS outputs. If max. 3 DCS outputs are used with these in-
struments, the following telegram can be used for data transmission:

Telegram from processing system to VEGACOM 557

Identifier: 1 character, optional "P“ or "p“
End identification: 1 character Chr (13) = CR = Carriage Return
Total length of the telegram: 5 characters

Answer of VEGACOM 557

Start character: S1 = 1 character "=“
Start character: S2 = "#“
Separating character: T1, T2, T3 = per 1
character "p“
Total length of the telegram: 32 characters

(structure also value for DCS value 2 and 3)

Error information
0: No error
1: Error on DCS 1
2: Error on DCS 2
3: Error on DCS 1+2
4: Error on DCS 3
5: Error on DCS 1 + 3
6: Error on DCS 2 + 3
7: Error on DCS 1,2 + 3

"-“ for negative values
" " for positive values

7

1 2 3 4 5 6

3 positions in front of the decimal point
1 decimal point
1 position after the decimal point

1 during simulation
" " during operation

Data image in VEGACOM 557

Address Address End

Identifier

VEGACOM

VEGAMET identification

No. of bytes

1

1

2

1

Range (ASCII)

p (P)

0..9

01..15

CR

Example

p

1

02

CR

Addr Addr

DCS

DCS

DCS

Error

End

S1 COM MET S2 value1 T1 value2 T2 value3 T3

info

identification

No. of bytes 1

1

1

1

7

1

7

1

7

1

1

2

Range (ASCII) = 0..9 01..15 # ASCII p ASCII p ASCII p

0..7

CRLF

Example =

1

02

#

17.2

p

38.4

p

45.7

p

0

CRLF