Electrical connection vegamet 514d s2, Technical data, Product description – VEGA VEGAMET 514D S2 User Manual

Page 3

Advertising
background image

VEGAMET 514D S2

3

Product description

2

28

24

22

30

32

d b z

+

-

+

-

+

-

+

-

-

+

L (+)
N (-)

6

10

12

+

20

16

18

+

-

+

Electrical connection

VEGAMET 514D S2

Supply
voltage

Fail safe relay

Relay output 1

Sensor

(current source)

DISBUS output

Current output

Voltage output

Correction signal
input
(input 4)

Relay output 2

Technical data

Measured data input

Quantity

1 input

Input type

passive two-wire input, analogue (sensor

delivery a flow-dependent current to the
signal conditioning instrument)

Range

4 … 20 mA

Possible sensors (loop powered)

active sensors (current sources)

Detection line interruption

< 3.6 mA

Detection line short-circuit

> 21 mA

Min. adjustment delta

2 % of the entered sensor values

Connection cable

2-wire standard cable (screening is
recommended)

max. resistance per wire

35 Ohm

Resolution

1 µA

Linearity error

0.025 % at 4 … 20 mA

Temperature error

0.04 %/10K at 4 … 20mA

For further technical data see VEGAMET 514D.

For further technical data see VEGAMET 514D.

For further technical data see VEGAMET 514D.

For further technical data see VEGAMET 514D.

For further technical data see VEGAMET 514D.