background image

6

VEGADIS 10

4 Set-up

Loosen the four screws on the upper side of
VEGADIS 10 and remove the housing cover
or the indicating module.

OK

Tighten the screws

Adjustment module

Connection and adjustment of VEGADIS 10
can be facilitated by lossely fastening the
housing cover or the indicating module with
two of t he screws laterally or dis placed to the
bottom.

The set-up and adj ustment of the VEGABAR
process pressure transmitter by means of
VEGADIS 10 corresponds exactly to the
procedure dir ectly on VEGABAR (see oper -
ating instructions VEGABAR…).
Furthermore, the different electronic versions
of VEGADIS 10 correspond to the electr onic
versions of VEGABAR.

Electronics B:
VEGADIS is only used as indicating instru-
ment.
Electronics C:
Adjustment of the basic functions
Electronics D:
Menu-guided adjustment with additional
functions

3 Electrical connection

Electrical connection, set-up

8

7

6

5

3

2

1

8

7

6

5

4

3

2

1

+

External energy
12 … 36 V DC
4 … 20 mA

max. 25 m

VEGABAR

VEGADIS 10 (with or without indication)

3.1 Connection instructions

Note:
Before starting connection, switc h off the
power supply of all components.

VEGADIS 10 can be connected to VEGABAR
process pressure transmitters with a 4-wire
standard cable (max. length 25 m). An exter -
nal energy sour ce is not necessar y.
Screened cable is re commended, if strong
electromagnetic interferences are expected.
Screening should be carried out from one
sensor end.

3.2 Connection plan