VEGA VEGAMET 381 User Manual

Page 26

Advertising
background image

26

6 Setup with the integrated display and adjustment unit

VEGAMET 381 • 4 … 20 mA signal conditioning instrument

27567-01-131025

ply and measurement data are transmitted

over the same two-wire cable. This mode is

provided for connection of measuring trans-

ducers without separate operating voltage

(sensor in two-wire version).

In passive mode, the sensors are not

powered, only the measurement value

is transmitted. This mode is provided for

connection of transmitters with their own

separate operating voltage (sensors in four-

wire version).

Set the function switch to position [F] and

select the suitable mode with the [+/-] keys.

Save your settings by pushing both keys

simultaneously.

Offset correction

When a pressure transmitter is used, an offset

correction should be carried out first. These

instruments are factory-set in a certain position.

If the pressure transmitter is now mounted in a

different position, its measuring range is shifted

slightly. The zero point is readjusted by carrying

out the offset correction in uncovered (unpres-

surised) condition. The complete measuring

range will be shifted by the deviating amount.
1. Make sure that the pressure transmitter

is completely unpressurised, uncovered

(unimmersed) and mounted in its final posi-

tion.

2. Set the function switch to position [A ]. The

display indicates now the actual sensor

current in mA. Save the current status by

pushing the [+/- ] keys simultaneously.

Adjustment in mA without changing the

level

For this adjustment procedure, two sensor

current values (4 … 20 mA) must be entered

corresponding to the levels 0 % and 100 %.
When using a pressure transmitter, an offset

correction should be carried out to reach maxi-

mum accuracy. Carry out this offset correction

before adjustment and with the sensor unco-

vered (unimmersed).

Now select the position [D] or [E] on the

function switch, enter the current values in

mA for min. or max. adjustment and save

your settings.

Adjustment in % by changing the level

During this adjustment procedure, the cur-

rent level is assigned to a certain percentage

value. For this reason, percentage values that

correspond to the actual filling levels must be

entered for the min. and max. adjustment. The

ideal calibration is at 0 % and 100 %. Because

it is not always possible to empty or fill a

vessel completely, any value can of course be

entered. The greater the difference between

the two adjustment points, the more precise the

measurement. It does not matter which value is

entered first.

Select position [B] or [C] on the function

switch, enter the percentage values for the

min. and max. adjustment and save your

settings.

Relay outputs

Two operating relays are integrated inVE-

GAMET 381 for level detection. First of all,

determine at which switching points the relays

should switch on and off again. Furthermore you

have to distinguish between the relay modes

overfill and dry run protection. You switch over

by exchanging the ON/OFF values of the relay.

Overflow protection: Relay is switched

off when the max. level is exceeded (safe

currentless condition), relay is switched on

again when the level falls below the min.

level (switch-on point < switch-off point)

Dry run protection: Relay is switched off

when the level falls below the min. level (safe

currentless condition), relay is switched

on again when the max. level is exceeded

(switch-on point > switch-off point)

To adjust the on and off switching points of

relay 1, set the function switch to position

[1] or [2], enter the switching points for ON

or OFF and save your settings. If necessary,

proceed in the same way with relay 2 (posi-

tion [3] or [4]).