4 mounting, 1 general instructions – VEGA VEGAPULS 66 (≥ 2.0.0 - ≤ 3.8) 4 … 20 mA_HART two-wire User Manual

Page 12

Advertising
background image

4 Mounting

4.1 General instructions

S

elect an installation position you can easily reach for mounting and

connecting as well as later retrofitting of an indicating and adjustment
module. The housing can be rotated by 330° without the use of any
tools. You can also install the indicating and adjustment module in four
different positions (each displaced by 90°).

U

se the recommended cables (see chapter "Connecting to power

supply") and tighten the cable gland.

Y

ou can give your instrument additional protection against moisture

penetration by leading the connection cable downward in front of the
cable entry. Rain and condensation water can thus drain off. This
applies mainly to outdoor mounting as well as installation in areas
where high humidity is expected (e.g. through cleaning processes) or
on cooled or heated vessels.

Fig. 2: Measures against moisture penetration

T

he reference plane for the measuring range is the lower edge of the

ange or the seal surface of the thread.

Mounting position

Moisture

Measuring range

12

VEGAPULS

66 • 4 … 20

mA/HART two-wire

4 M

ounting

28438

-EN

-090305

Advertising