Adjustment, Adjustment steps, Address – VEGA VEGAPULS 41 Profibus PA User Manual

Page 39: Measurement in a standpipe, Operating range

Advertising
background image

VEGAPULS 41 – Profibus PA

39

27292-EN-041227

Adjust-
ment

Para-
meter

Sensor

m(d)

4.700

w.o
medium

Ad-
just-
ment
in

m(d)

(min. adjustment)

OK

OK

OK

OK

4. Adjustment

Under the menu item "

Adjustment“ you inform

the sensor of the measuring range it should
operate in.

You can carry out the adjustment with or
without medium. Generally, you will carry out
the adjustment without medium, as you can
then adjust without a filling/emptying cycle.

Adjustment without medium

(adjustment independent of the level)

Key

Display indication

Max.

Min.

100 % (1.270 m) correspond
to 1200 liters

Span (4.58 m)

0 % (5.850 m) corresponds
to 45 liters

Adjustment steps

On the following pages you will find the com-
plete menu schematic of the adjustment mod-
ule MINICOM. Set up the sensor in the
numbered sequence:
1. Address
2. Measuring tube adjustments (only for

measurement in a standpipe)

3. Operating range
4. Adjustment
5. Conditioning
6. Meas. conditions
7. False echo storage (only required when

errors occur during operation)

8. Indication of the useful and noise level
9. Outputs
Outputs
Short explanations to the setup steps 1 … 9
follow.

1. Address

Choose a free bus address with the DIP
switch (see chapter „3.2 Sensor address“).

2. Measurement in a standpipe

Adjustment is only necessary if the sensor is
mounted in a standpipe (surge or bypass
tube). When measuring in a standpipe, do a
sounding of the distance and correct the
measured value display (which can differ
several percent from the sounded value)
according to the sounding. From then on, the
sensor corrects the running time shift of the
radar signal and displays the correct value of
the level in the standpipe (measuring tube).

3. Operating range

Without special adjustment, the operating
range corresponds to the measuring range.
It is generally advantageous to set the oper-
ating range slightly larger (approx. 5 %) than
for measuring range.

Example:
Min./max. adjustment: 1.270 … 5.850 m;
adjust operating range to approx.
1.000 … 6.000 m.

Set-up