Software addressing – VEGA VEGAPULS 45 Profibus PA User Manual

Page 34

Advertising
background image

34

VEGAPULS 42, 44 and 45 – Profibus PA

24908-EN-041227

Electrical connection

Example 2

You want to set address 27.
16 + 8 + 2 + 1 = 27

You must set the DIP switches
5 = 16
4 = 8
2 = 2
1 = 1
to „ON“.

Example 3

You want to set address 99
64 + 32 + 2 + 1 = 99

You must set the DIP switches
7 = 64
6 = 32
2 = 2
1 = 1
to „ON.

Software addressing

The DIP switches must be set to an address
of 126 … 255, i.e.

- either all DIP switches are set to „ON“,

which corresponds to address 255 (deliv-
ery status)

ON

Addr.

8 7 6 5 4 3 2 1

OFF

1

2

4

8

16

32

64

128

8 7 6 5 4 3 2 1

- or only DIP switch 8 is set to „ON“, which

corresponds to address 128.

Of course, software addressing is also pos-
sible, if the switches 7 … 2 are set to „ON“
(address 126).

The setting of the address with the software
VVO is described in chapter “5.2 Adjustment
with VVO” under the heading “Software ad-
dressing” or in chapter “5.3 Sensor adjust-
ment with the adjustment module MINICOM”.

Advertising