Supplement b – VEGA VEGACOM 558 Ethernet User Manual

Page 68

Advertising
background image

68

VEGACOM 558 Ethernet

Supplement A

Complete overview of the process image of switching status in
VEGACOM 558:

Supplement B

Register bit

address

in

Modicon

Module no.

No. of output

DISBUS address

Status /

Sw itching status

10.001

#1

Output contact 9

VEGAMET #1

Input contact 2

10.002

#1

Output contact 10

VEGAMET #1

Input contact 1

10.003

#1

-

VEGAMET #1

-

10.004

#1

-

VEGAMET #1

-

10.005

#1

-

VEGAMET #1

-

10.006

#1

-

VEGAMET #1

-

10.007

#1

-

VEGAMET #1

-

10.008

#1

Status: Card

VEGAMET #1

Status of inputs

10.009

#1

Output contact 1

VEGAMET #1

Relay contact 1

10.010

#1

Output contact 2

VEGAMET #1

Relay contact 2

10.011

#1

Output contact 3

VEGAMET #1

Fail saf e relay

10.012

#1

Output contact 4

VEGAMET #1

-

10.013

#1

Output contact 5

VEGAMET #1

-

10.014

#1

Output contact 6

VEGAMET #1

-

10.015

#1

Output contact 7

VEGAMET #1

-

10.016

#1

Output contact 8

VEGAMET #1

Status of outputs

10.017

#2

Output contact 9

VEGAMET #2

Input contact 2

10.018

#2

Output contact 10

VEGAMET #2

Input contact 1

10.019

#2

-

VEGAMET #2

-

10.020

#2

-

VEGAMET #2

-

10.021

#2

-

VEGAMET #2

-

10.022

#2

-

VEGAMET #2

-

10.023

#2

-

VEGAMET #2

-

10.024

#2

Status: Card

VEGAMET #2

Status of inputs

10.025

#2

Output contact 1

VEGAMET #2

Relay contact 1

10.026

#2

Output contact 2

VEGAMET #2

Relay contact 2

10.027

#2

Output contact 3

VEGAMET #2

Fail saf e relay

10.028

#2

Output contact 4

VEGAMET #2

-

10.029

#2

Output contact 5

VEGAMET #2

-

10.030

#2

Output contact 6

VEGAMET #2

-

10.031

#2

Output contact 7

VEGAMET #2

-

10.032

#2

Output contact 8

VEGAMET #2

Status of outputs

10.033

#3

Output contact 9

VEGAMET #3

Input contact 2

10.034

#3

Output contact 10

VEGAMET #3

Input contact 1

10.035

#3

-

VEGAMET #3

-

10.036

#3

-

VEGAMET #3

-

10.037

#3

-

VEGAMET #3

-

10.038

#3

-

VEGAMET #3

-

10.039

#3

-

VEGAMET #3

-

10.040

#3

Status: Card

VEGAMET #3

Status of inputs

10.041

#3

Output contact 1

VEGAMET #3

Relay contact 1

10.042

#3

Output contact 2

VEGAMET #3

Relay contact 2

10.043

#3

Output contact 3

VEGAMET #3

Fail saf e relay

10.044

#3

Output contact 4

VEGAMET #3

-

VEGALOG

VEGAMET

513, 514, 515, 614

Advertising