Vessel without cathodic corr osion pr otection, Electrical connection, Ex) area zone1 non (ex) area – VEGA Capacitive electrodes EK 4 … 20 mA - Compact User Manual

Page 23

Advertising
background image

Capacitive electrodes EK 4 … 20 mA - Compact

23

22574-EN-020809

Electrical connection

V

essel without cathodic corr

osion pr

otection

A

B

A2

A1

E2

E1

2

1

2

1

E2

E1

A2

A1

Overvoltage
protection unit
mounted on
oscillator

Oscillator

CB
2-36

C A P
E32(H)EX

Vessel
Zone 0

Oscillator
Li=0.12 mH
Ci=6 nF

External ground terminal

Internal ground terminal

Vessel
Zone 0

CAP
E32
(H)Ex

External ground terminal

Internal ground terminal

Li, Ci of the oscillator with overvoltage
protection unit
Li = 0.27 mH
Ci = 8.5 nF

(Ex) area Zone1

Non (Ex) area

Signal
condit-
ioning
instru-
ment
or
safety
bar-
rier

Control room
optionally:
Overvoltage
protection insert

Typ B62-36G

Li=0.15 mH
Ci=2.5 nF

Overvoltage protection insert

Typ
B62-36G
Li=0.15 mH
Ci=2.5 nF

Insulated cable
min. 4 mm

2

*
**

Screen

A

B

Overvoltage arrester type
B62-36 G in metal or plastic
housing

**

to the potential equali-
sation line

Screen

to the potential equalisa-
tion line

b)Capacitive electrodes with external
overvoltage protection unit

a) Capacitive electrodes with integrated
overvoltage protection unit type CB 2-36

A suitable cable, if necessary with metal
cover or screen, must be used between
control room and overvoltage protection
system. Metal cover or screen - if necessary
- should only be connected with one cable
end to ground or PA.
Test voltage of cable A: • 500 V AC

A suitable cable with metal cover, screen or a
suitable cable in a protective metal tube must
be used between overvoltage protection
system and capacitive electrode (metal cover
or protective tube must be connected to the
potential equalisation)
Test voltage of cable B: • 1500 V AC

* optional
Connect screen only on one
cable end to ground or PA

** optional
Connect screen only on one
cable end to ground or PA

Advertising