6 setup – VEGA VEGASWING 61 - NAMUR User Manual

Page 17

Advertising
background image

17

6 Setup

VEGASWING 61 • - NAMUR

29226-EN-130409

6 Setup

6.1 General information

The figures in brackets refer to the following illustrations.

With plastic housings, the switching condition of the electronics can

be checked when the housing cover is closed (control lamp). With the

basic setting, products with a density > 0.7 g/cm³ (0.025 lbs/in³) can

be detected. For products with lower density, the switch must be set

to > 0.5 g/cm³ (0.018 lbs/in³).
On the electronics module you will find the following indicating and

adjustment elements:

Signal lamp (1)

DIL switch for characteristics reversal - min./max. (2)

DIL switch for sensitivity adjustment (3)

Simulation key (4)

Note:

For test purposes, immerse the tuning fork of VEGASWING 61 always

in liquids. Do not test the function of VEGASWING 61 with your hand.

This can damage the sensor.

6.2 Adjustment elements

1

5

2

3
4

Fig. 12: Oscillator SWE60N - NAMUR output
1 Signal lamp (LED)

2 DIL switch for characteristics reversal

3 DIL switch for sensitivity adjustment

4 Simulation key

5 EMC filter element

Single-coloured control lamp for indication of the switching condition.

red = High current ≥ 2.6 mA

dark = Low current ≤ 0.6 mA

red (flashing) = Failure ≤ 0.6 mA

Function/Configuration

Signal lamp (1)

Advertising