7 maintenance and fault rectification, 1 maintenance, 2 rectify faults – VEGA VEGACAP 64 - transistor (NPN_PNP) User Manual

Page 22

Advertising
background image

22

7 Maintenance and fault rectification

VEGACAP 64 • - transistor (NPN/PNP)

30014-EN-130916

7 Maintenance and fault rectification

7.1 Maintenance

If the instrument is used properly, no special maintenance is required

in normal operation.

7.2 Rectify faults

The operator of the system is responsible for taking suitable meas-

ures to rectify faults.

VEGACAP 64 offers maximum reliability. Nevertheless, faults can oc-

cur during operation. These may be caused by the following, e.g.:

Sensor

Process

Voltage supply

Signal processing

The first measure to be taken is to check the output signal. In many

cases, the causes can be determined this way and the faults rectified.

Should these measures not be successful, please call in urgent cases

the VEGA service hotline under the phone no. +49 1805 858550.
The hotline is available to you 7 days a week round-the-clock. Since

we offer this service world-wide, the support is only available in the

English language. The service is free of charge, only the standard

telephone costs will be charged.

Error

Cause

Rectification

– The instrument

signals covered

without cover-

ing with the

medium

– The instrument

signals covered

with cover-

ing with the

medium

Wrong mode se-

lected

Set the correct mode on the mode

switch (max.: overfill protection, min.:

dry run protection)

Operating voltage

too low

Check operating voltage

Shortcircuit in the

probe, e.g. be-

cause of moisture

in the housing

Remove the electronics module.

Check the resistance between the

marked plug connections. See the fol-

lowing instructions.

Electronics de-

fective

– Push mode switch (min./max.)

ƴ

If the probe then does not

change the mode, the electron-

ics module may be defective.

Exchange the electronics module

ƴ

If the instrument then

changes the mode, the instrument

is mechanically damaged. Should

the switching function in the cor-

rect mode still be faulty - return

the probe for repair.

Reaction when malfunc-

tions occur

Failure reasons

Fault rectification

24 hour service hotline

Checking the switching

signal

Advertising