VEGA VEGAPULS 68 (≥ 2.0.0 - ≤ 3.8) 4 … 20 mA_HART four-wire User Manual
Page 17
Advertising
1
2
Fig. 7: Mounting position
1
Reference plane
I
f you cannot keep this distance you should carry out a false echo
storage before setup. This applies mainly if buildup on the vessel wall
is expected. In this case, we recommend repeating a false echo
storage later with existing buildup.
T
o measure as much of the vessel volume as possible, the sensor
should be aligned so that the measuring beam reaches the lowest
level in the vessel. In a cylindrical silo with conical outlet, the easiest
way is to mount the instrument in the center of the silo.
Orientation
VEGAPULS
68 • 4 … 20
mA/HART four-wire
17