VEGA VEGACAL 63 4 … 20 mA_HART - two-wire User Manual

Page 27

Advertising
background image

27

6 Set up with the display and adjustment module PLICSCOM

VEGACAL 63 • 4 … 20 mA/HART - two-wire

30027-EN-130917

and 90 %. The difference between the empty and full adjustment

values should be as large as possible.
The actual level can then be calculated on the basis of these settings.
VEGACAL 63 must be installed. A change of level is necessary for

this adjustment.
In the main menu item "Basic adjustment", the individual submenu

items should be selected one after the other and provided with the

correct parameter values.

Tip:

If the display and adjustment module remains on the probe as a

display, we recommend saving the sensor data in the display and

adjustment module.
Use the function "Copy sensor data".
Start your parameter adjustment with the following menu items of the

basic adjustment:

To be on the safe side, note the adjustment values for full and empty.

If an adjustment procedure fails, it is not necessary to again carry out

a level change.
These values can be helpful if the electronics has to be exchanged.

%

Value

Empty adjustment
Full adjustment

Tab. 1: Adjustment protocol

Tip:

For min. adjustment the vessel should be as empty as possible, and

for max. adjustment, as full as possible. If the vessel is already full,

start with max. adjustment.
Note:

If possible, the vessel should be as empty as possible for min. adjust-

ment.
Proceed as follows:
1. Move from the measured value display to the main menu by

pushing [OK].

Basic adjustment
Display
Diagnostics
Service
Info

2. Select the menu item "Basic adjustment" with [->] and confirm

with [OK]. Now the menu item "Min. adjustment" is displayed.

Min. adjustment
0.00 %
=
0.0 pF

54.5 pF

Carry out min. adjustment

Advertising