VEGA VEGACAL 66 Foundation Fieldbus User Manual

Page 26

Advertising
background image

26

6 Set up with the display and adjustment module PLICSCOM

VEGACAL 66 • Foundation Fieldbus

30038-EN-130917

Tip:

If the display and adjustment module remains on the probe as a

display, we recommend saving the sensor data in the display and

adjustment module.
Use the function "Copy sensor data".
Start your parameter adjustment with the following menu items of the

basic adjustment:

To be on the safe side, note the adjustment values for full and empty.

If an adjustment procedure fails, it is not necessary to again carry out

a level change.
These values can be helpful if the electronics has to be exchanged.

%

Value

Empty adjustment
Full adjustment

Tab. 1: Adjustment protocol

Tip:

For min. adjustment the vessel should be as empty as possible, and

for max. adjustment, as full as possible. If the vessel is already full,

start with max. adjustment.
Note:

If possible, the vessel should be as empty as possible for min. adjust-

ment.
Proceed as follows:
1. Move from the measured value display to the main menu by

pushing [OK].

Basic adjustment
Display
Diagnostics
Service
Info

2. Select the menu item "Basic adjustment" with [->] and confirm

with [OK]. Now the menu item "Min. adjustment" is displayed.

Min. adjustment
0.00 %
=
0.0 pF

54.5 pF

3. Prepare the adjustment value for editing with [OK]. Move to the

selection window with [OK].

Min. adjustment

Accept current measured

value?

Accept?

Edit?

4. Accept the current measured value or move to the editing window

with "Edit". To edit, set the cursor to the requested position with

Carry out min. adjustment

Advertising